Troubleshooting
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
72
Sys (System Status) Tricolor LED
Color
Pattern
Condition
Message in Module
Status
Possible Solution
Red
2 blink
Restarting after an abnormal exit
Auto restart delay due
to system error on
startup
After 5 minute delay has
expired, if condition occurs
again then cycle power
Red
4 blink
Firmware image is corrupt
Firmware error
Download driver again
Red
Fast
blink
Firmware error has caused the
firmware to exit and restart
Fatal error detected
No action required
Green
1 blink
No errors
Operational
No action required
Green
2 blink
Download of driver is in progress
Download in progress
No action required
Green
3 blink
BACnet Device ID is not set
Download required
Download the controller
Green
Fast
blink
Installation of recently downloaded
driver is occurring
N/A
No action required
Blue
On
Controller is starting up
N/A
No action required
Blue
Slow
blink
Linux (operating system) is starting up
N/A
No action required
Blue
Fast
blink
Linux is running but it could not start
the firmware application
N/A
Download driver
Magenta
Operating system changes are
downloading
WARNING
This process could take
several minutes. Do NOT power off the
controller during the download.
N/A
No action required