Wiring inputs and outputs
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
37
3
Connect the input wiring to the
UI
screw terminals on the TV-MPCXP1628-NR.
WARNING
Do not apply voltage to any input configured for 0-20 mA as this could damage the
expander.
NOTE
Connect the shield wire to the
–
terminal with the ground wire. Do not connect the shield wire at the
other end of the cable as this will cause a ground loop error.
Dry
contact
Any input
-
-
-
-
-
-
-
-
-
External
24 Vdc
half-wave
power
supply
2 wire
3 wire
24 Vdc
connector
Out
V+
Gnd
+
Any input
+
Any input
+
Any input
+
Any input
+
Any input
+
Any input
+
Out
V+
Any input
+
10 kOhm
thermistor
1 kOhm
RTD
n/c
4 wire
2 wire
3 wire
4 wire
Out +
Out -
V+
Gnd
Any input
+
Out
V+
Gnd
Out
V+
n/c
Out +
Out -
V+
Gnd
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
NOTE
For a loop-powered 4-20 mA sensor, wire the sensor's positive terminal to the
+
terminal on the TV-
MPCXP1628-NR's
24 Vdc
connector. Wire the sensor's negative terminal to an input's
+
terminal.