Troubleshooting
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
74
Troubleshooting inputs and outputs
The i-Vu® interface shows if you have I/O errors resulting from:
•
A misconfigured microblock
•
A misconfiguration on the expander
•
A missing or disconnected expander
To check for errors:
1
In the i-Vu® navigation tree, select the equipment controlled by the TruVu MPC Controllers TV-MPCXP1628-
NR.
2
On the
Properties
page, select the
I/O Points
tab.
3
Click the
Name
of any input or output whose name is red (indicates an error) to open its dialog box.
4
On the
Details
tab, scroll down to see the
Reliability
field under
BACnet Configuration
.
5
Anything other than
No Fault Detected
indicates an error. See the table below to determine the error and
possible actions to take.