4–35
T-340
Cd70
Temp Setpoint Lock
Cd70 locks out setpoint selection, requiring the user to manually turn the lock off,
prior to making a setpoint change. If the setpoint lock is “ON”, and the user at
-
tempts to enter a new setpoint, a message “SPLK” (Setpoint Lock) is in the left
display and “ON” in the right display for five seconds.
Press the ENTER key. “SPLK” will display along with the current setting of “ON”
or “OFF”. Use the Arrow keys to change the selection - the new selection will
then flash for five seconds. Press the ENTER key to confirm the new selection.
An event will be recorded in the DataCORDER each time the action of turning it
“ON” or “OFF” is taken.
Default setting is “OFF”. Unit will default to “OFF” with the selection of PTI or a
TripWise on the unit.
Table 4–5 Controller Function Codes
Code
Title
Description
Содержание Transicold 69NT40-561-001
Страница 2: ......
Страница 4: ......
Страница 14: ......
Страница 22: ......
Страница 36: ......
Страница 92: ......
Страница 159: ...7 47 T 340...
Страница 163: ...8 3 T 340 Figure 8 2 Schematic Diagram for Standard Unit Configuration Based on Drawing 62 11271 Rev A...
Страница 169: ...8 9 T 340 Figure 8 8 Schematic and Diagram for Lower Vent Position Sensor VPS Option...
Страница 170: ...T 340 8 10 Figure 8 9 Unit Wiring Diagram for Standard Unit Configuration With 3 Phase Condenser Fan Motors...
Страница 172: ...T 340 8 12 Figure 8 10 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater...
Страница 173: ...8 13 T 340 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater Based on Drawing 62 66721...
Страница 174: ...T 340 8 14 Figure 8 11 Unit Wiring Diagram for Configuration With eAutoFresh and Emergency Bypass Options...
Страница 176: ......
Страница 180: ......
Страница 181: ......