Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
68
ZS Zone Humidity
- Configure additional ZS humidity sensors used on the RTU Open.
•
Use
- Check to include ZS sensors' value in the
Combined Algorithm
(
Maximum
is
the default).
•
Raw Value
- Displays sensed humidity for each ZS humidity sensor's address
•
Calibration
- If needed, enter value to adjust the
Corrected Value
from the
Raw
Value
, in order to calibrate an individual ZS sensor's sensed value.
•
Combination Algorithm
- Use
Average
,
Maximum
, or
Minimum
ZS humidity to
calculate the
Corrected Value
for humidity control.
D:
(Index) Area
- (1) Main ZS
Sensor
Use -
unchecked
Calibration
- 0
Combination Algorithm
-
Maximum
Input Smoothing
-
Medium
Show on Sensors
-
Calculated Value
Display Resolution
- 1
COV Increment
- 1
ZS Zone CO2
- Configure additional ZS CO
2
sensors used on the RTU Open.
•
Use
- Check to include ZS sensors' value in the
Combined Algorithm
(
Maximum
is
the default).
•
Raw Value
-Displays sensed CO
2
for each ZS CO
2
sensor's address
•
Calibration
- If needed, enter value to adjust the
Corrected Value
from the
Raw
Value
, in order to calibrate an individual ZS sensor's sensed value.
•
Combination Algorithm
- Use
Average
,
Maximum
, or
Minimum
ZS CO
2
to calculate
the
Corrected Value
for CO
2
control.
D:
(Index) Area
- (1) Main ZS
Sensor
Use -
unchecked
Calibration
- 0
Combination Algorithm
-
Maximum
Input Smoothing
-
Medium
Show on Sensors
-
Calculated Value
Display Resolution
- 1
COV Increment
- 10
ZS model to show on graphic
- Select the ZS model, from the drop-down list, that you
want to display on the graphic.
D:
R:
ZS Pro-F model
None
ZS Pro model
ZS Base model
ZS Plus model
ZS Pro-F model