Appendix B: Single Point Linkage and Device Address Binding
RTU Open v3
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
92
Device Address Binding
Device Address Binding
(DAB) allows the controller to receive data from other Open controllers when they are
connected by a network. The controller receives data from other Open or BACnet controllers when they are
installed as part of an i-Vu® Control System. The data transfer takes the form of DAB, which you must configure.
Currently, the controller implements DAB for the following variables:
•
System Outdoor Air Temperature
•
System Occupancy
•
System Leaving Load Water Temp
•
System Control Setpoint
•
System Cool Demand Level
•
System Space RH
You can implement DAB on network points with an undefined BACnet address, displayed in Field Assistant and the
i-Vu® interface on the
Properties
page >
Network Points
tab. See example below.