Appendix C: RTU Open Points/Properties on the Equipment Touch
RTU Open v3
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
103
Point Name/Description
Default/Range
Active Compressor Stages –
The number of compressor stages currently operating.
R: 0 to 2
Active Heat Stages –
The number of heating stages currently operating.
R: 0 to 2
Enthalpy (BACnet)
– The enthalpy status the controller receives through BACnet
communication.
R: High (0) / Low (1)
Reset Supply Fan Runtime Alarm
– Set to
Clear
to reset
Supply Fan Runtime
to 0.
D:
R:
Run
Run/Clear
Reset Filter Runtime Alarm
– Set to
On
to reset
Filter Runtime
to 0.
D:
R:
Run
Run/Clear
Occupancy
BAS On/Off
– Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Options:
Inactive
– Occupancy is determined by a configured schedule.
Occupied
– The controller is always in the occupied mode.
Unoccupied
– The controller is always in the unoccupied mode.
NOTE
If
BAS On/Off
is set to either
Unoccupied
or
Occupied
, the
Optimal Start
routine
is automatically disabled.
D:
R:
Inactive
Inactive
Occupied
Unoccupied
Pushbutton Override
–
Active
indicates if a user pushed the sensor's override button to
override the occupancy state.
R: Off/Active
Override Time Remaining
– The amount of time remaining in an override period.
R: 0 to 240 minutes
Schedule
– The controller's occupancy status based on the local schedule.
R: Unoccupied/Occupied
Airside Linkage
Airside Linkage Status
R: OFF
WARMUP
HEAT
COOL
FREECOOL
PRESSURIZE
EVAC
VENT
NOT ACTIVE