Installing the RTU Open
RTU Open v3
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
13
Wiring inputs and outputs
RTU Open Inputs and Outputs Table
Channel
Number
Type
Signal
Function
Part Number
Wire and
Terminal
Numbers
Alternate
Terminals
Input 1
AI
4-20 mA
CO2
OAQ
Space Relative Humidity
33ZCT55CO2 33ZCT56CO2
33ZCSPTCO2-01
33ZCSPTCO2LCD-01
w/ 33ZCASPCO2
33ZCSENSRH-02
J4
- 5 & 6
N/A
Input 2
AI
4-20 mA
CO2
OAQ
Space Relative Humidity
33ZCT55CO2 33ZCT56CO2
33ZCSPTCO2-01
33ZCSPTCO2LCD-01
w/ 33ZCASPCO2
33ZCSENSRH-02
J4
-
2 & 3
N/A
Input 3
BI
24 Vac
Compressor Safety **
2
Fan Status
Filter Status
Remote Occupancy
Door Contact
N/A
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J1
-
2
J5
- 5 & 6 ***
Input 4
BI
24 Vac
Safety Chain
*
N/A
J1
- 9
N/A
Input 5
BI
24 Vac
Fire Shutdown **
1,
2
Fan Status
Filter Status
Remote Occupancy
Door Contact
Field-supplied
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J1
- 10
J5
- 3 & 4 ***
Input 6
AI
10K
Thermistor
Supply Air Temperature
33ZCSENSAT 33ZCSENDAT
J2
- 1 & 2
N/A
Input 7
AI
10K
Thermistor
Outside Air Temperature
33ZCSENOAT
J2
- 3 & 4
N/A
Input 8
BI
24 Vac
Enthalpy **
Fan Status
Filter Status
Remote Occupancy
Door Contact
33SENTHSW
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J2
- 6 & 7
J5
- 1 & 2 ***
Input 9
BI
24 Vac
IGC Input****
Humidistat **
Fan Status
Filter Status
Remote Occupancy
Door Contact
--HL--38MG-029
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J5
- 7 & 8
N/A
Input 10
AI
10K
Thermistor
Space Temperature
33ZCT55SPT 33ZCT56SPT
33ZCT59SPT
J20
- 1 & 2
N/A
Input 11
AI
100K
Thermistor
Space Temperature
Setpoint Adjust
33ZCT56SPT 33ZCT59SPT
J20
- 3 & 4
N/A
Rnet
AI
ZS sensors
Wireless Adapter for
wireless sensors
Equipment Touch
TruVu™ ET Display
See Wiring devices to the Rnet
port.
J13
- 1, 2, 3,
4
N/A
AO - 1
AO
4-20 mA
Economizer
Actuator-Field-supplied
J2
- 5 & 4
N/A