Installing the RTU Open
RTU Open v3
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
18
J4 Inputs
1
Turn
off
the RTU Open's power.
2
Connect the input and output wiring to the screw terminals on the RTU Open.
NOTE
When utilizing the controller's 24 Vdc auxiliary power out, the total current demand for these two input
channels must not exceed 40 mA (or a maximum of 25 mA per channel).
NOTE J4
Analog Inputs 1 and 2 may be set for the following device types:
•
IAQ Sensor
•
OAQ Sensor
•
Space RH Sensor
J5 Inputs
The terminals for Inputs 3, 5, and 8 are available for use in place of the flying wire leads at Molex connectors J1
and J2 identified below:
NOTE
J5
binary inputs 3, 5, and 8 are the same input channels as:
•
J1
wire
2,
J5 - 5
Input - 3 (
Compressor Safety
)
•
J1
wire
10,
J5 - 3
Input - 5 (
Fire Shutdown
)
•
J2
wire 6,
J5
-
1
Input - 8 (
Enthalpy Switch
).