all
(all)
(all)
(unit_typ = 3)
(unit_typ = 1 or 4)
(all)
(all)
(all)
(all)
(uni_typ = 1 or 4)
H-DIM
-
Basic board multilexed DI's:
b
7
b
6
b
5
b
4
b
3
b
2
b
1
b
0
b
0
:
onoff_sw
Remote on/off switch
b
1
:
spt_sw
Remote dual setpoint sw
b
2
:
hc_sw
Remote heat/cool switch
b
2
:
recl_sw
Remote reclaim swutch
b
3
:
limit_sw
demand limit switch
b
4
:
lock_1
Cooler interlock
b
5
:
elec_box
Electrical Box Thermostat
b
6
:
condflow
Condenser flow switch
b
7
:
pump_def
Pump default
MUX_DI
econ_sel and tq_r_fbk=
YES
H-AI
-
Motor Cooling Feedback Signal circuit B
MTQ_RESB
econ_sel and tq_r_fbk=
YES
H-AI
-
Motor Cooling Feedback Signal circuit A
MTQ_RESA
recl_opt = 1
H-AO
0 -
10Vdc
Reclaim Condenser Water Valve
HR_WTRVL
hr_tmp = 1
H-AI
°F
Reclaim Entering Water Temperature
HR_LWT
hr_tmp = 1
H-AI
°F
Reclaim Entering Water Temperature
HR_EWT
hd_selec > 0
H-AO
4 - 20
mA
0 -
10Vdc
Varifan or Water Valve Circuit B
HD_B
hd_selec > 0
H-AO
4 - 20
mA
0 -
10Vdc
Varifan or Water Valve Circuit A
HD_A
cb2_mta> 0
H-AI
psi
Discharge Pressure Circuit B
DP_B
all
H-AI
psi
Discharge Pressure Circuit A
DP_A
all
H-AI
volts
External 0 - 10 Vdc input sensor
EXT_VDC
cb2_mta > 0
H-AO
%
EXV Movement Circuit B
EXV_ST_B
all
H-AO
%
EXV Movement Circuit A
EXV_ST_A
cb2_mta> 0
H-AI
-
Compressor B2, status and MTA reading
CPB2_STA
cb2_mta> 0
H-AI
°F
Compressor B2, Motor Temperature
CPB2_TMP
cb2_mta> 0
H-AI
°F
Compressor B2, Discharge Gas Temperature
CPB2_DGT
cb2_mta > 0 and
econ_sel = 0
H-AI
psi
Compressor B2, Economizer Pressure
CPB2_ECP
CONFIGURATION
TYPE
UNITS
DESCRIPTIONS
POINT
NAMES
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: Original
Page: 78/98
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION