SETPOINT SCREEN
TABLE NAME: SETPOINT PIC TABLE TYPE : 17H, instance 1
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
1
COOLING
2
Cooling Setpoint 1
- 20 to 101
44.0
°F
csp1
3
Cooling Setpoint 2
- 20 to 101
44.0
°F
csp2
4
Voltage No Reset Value
0 to 10
0.0
volts
v_cr_no
5
Voltage Full Reset Value
0 to 10
0.0
volts
v_cr_fu
6
Delta T No Reset Value
0 to 25
0.0
^F
dt_cr_no
7
Delta T Full Reset Value
0 to 25
0.0
^F
dt_cr_fu
8
OAT No Reset Value
14 to 125
0.0
°F
oatcr_no
9
OAT Full Reset Value
14 to 125
0.0
°F
oatcr_fu
10
Cooling Reset Deg. Value
-30 to 30
0.0
^F
cr_deg
11
Cooling Ramp Loading
0.2 to 2.0
1.0
^F
cramp_sp
12
13
HEATING
14
Heating Setpoint
80 to 153
100.0
°F
hsp
15
Voltage No Reset Value
0 to 10
0.0
volts
v_hr_no
16
Voltage Full Reset Value
0 to 10
0.0
volts
v_hr_fu
17
Delta T No Reset Value
0 to 25
0.0
^F
dt_hr_no
18
Delta T Full Reset Value
0 to 25
0.0
^F
dt_hr_fu
19
Heating Reset Deg. Value
-30 to 30
0.0
^F
hr_deg
20
Heating Ramp Loading
0.2 to 2.0
1.0
^F
hramp_sp
21
22
HEAD PRESSURE
23
Sat Cond Temp Setpoint
95 to 140
1
104.0
°F
headsp
24
Reclaim Setpoint
95 to 140
122.0
°F
rsp
25
26
DEMAND LIMIT
27
Switch Demand Limit Setp
0 to 100
100
%
lim_sp
1 : For water cooled, headsp low limit is 80°F (26.7 degC)