3.2 - Basic Board
The PD4 - Basic board is 24VAC power supplied. It contains 8 Discrete Inputs (Switch type), 8 Digital Outputs (5
triacs and 3 relays), 10 Analog Inputs (five thermistors and four pressure transducers) and 1 analog input (0-10
Vdc) . See the schemes in Appendix E. The software is contained in a Flash EPROM (downloadable only with
Downloader). All the setpoints, runtime and configuration parameters are contained in an EEPROM (data
storage at power down).
All
Safety Critical Signal (for Contactor Failure)
26
J3
All
Alarm Circuit B
25
J3
All
Alarm Circuit A
24
J3
Air cooled
Oil Heater Circuit B
23
J2
Air cooled
Oil Heater Circuit A
22
J2
All excepted air cooled without
reclaim option
Condenser Pump
21
J2
All
Cooler Pump #2
20
J2
All
Cooler Pump #1
19
J2
All
Cooler pump default
18
J5
All excepted air cooled without
reclaim option
Condenser flow switch
17
J5
All
Electrical box thermostat & network power reverse
phase detection
16 a & 16 b
J5
All
Cooler flow switch & customer interlock (lock_1)
15 a & 15 b
J4 & J5
All
Demand limit switch
14
J4
All excepted heat machine
Heat Reclaim switch
13
J4
Heat machine
Heat Cool switch
13
J4
All
Dual setpoint switch
12
J4
All
Remote Control switch status
11
J4
All
0-10 VDC setpoint reset signal or demand limit signal
10
J8
All
Circuit B suction pressure
9
J7D
All
Circuit B discharge pressure
8
J7C
All
Circuit A suction pressure
7
J7B
All
Circuit A discharge pressure
6
J7A
Water cooled and heat pump
Condenser entering water temperature
5
J6
Water cooled and heat pump
Condenser leaving water temperature
4
J6
Air cooled
Outside Temperature
4
J6
Master/Slave
Master/Slave common piping fluid temperature
3
J6
All
Cooling entering water temperature
2
J6
All
Cooling leaving water temperature
1
J6
UNIT TYPE
FUNCTION
CHANNEL
TERMINAL
3.2 - CCN/Clock Option Board
(factory installed)
The PD4 - Global chiller controller has a small option board that can be connected to the Basic Board via a
single 10 pin header and 4 metal standoff. This option board contains one RS-485 driver for CCN
communication, a real time clock and super cap for two weeks backup. There are two connectors for CCN. One
is a 3 pin screw connector ( 1= + signal, 2 = ground signal, 3 = - signal) and the other is a 6 pins phone jack.
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG-UG-02-002
Rev: original
Page: 10/98
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION