4.2.3 - Factory configuration
4.2.3.1 - Factory configuration from Service Tool
The Network Service tool allows to view and modify the factory configuration (table FACTORY in 'Modify
Controller').
TABLE NAME: FACTORY PIC TABLE TYPE : 10H, instance 1
DESCRIPTION
STATUS
DEFAULT UNITS
POINT
1
Chiller Type
1,2,3
1
1
-
unit_typ
2
Circuit A Fan Stages Num
0 to 8
2
0
-
nb_fan_a
3
Circuit B Fan Stages Num
0 to 8
2
0
-
nb_fan_b
4
Varifan or W. Valves Sel
0/1/2/3/4
0
-
hd_selec
5
Economizer Select
Yes/No
3
No
-
econ_sel
6
Large Bd Oil Transducers
Yes/No
4
No
-
oil_sel
7
Comp A1 Must Trip Amps
0 to 560
5
0
-
mta_cpa1
8
Comp A2 Must Trip Amps
0 to 560
5
0
-
mta_cpa2
9
Comp B1 Must Trip Amps
0 to 560
5
0
-
mta_cpb1
10
Comp B2 Must Trip Amps
0 to 560
5
0
-
mta_cpb2
11
Reclaim Sensor Select
Yes/No
6
No
-
hr_tmp
12
Air Cooled Reclaim Sel
Yes/No
7
No
-
recl_opt
13
Evaporator Number Pass
1 to 3
8
3
-
evap_pas
14
Cooler LWT On Circuit A
Yes/No
9
Yes
-
cira_lwt
15
Cooler Heater Select
Yes/No
10
No
-
heat_sel
16
Factory Password
0 to 150
11
113
-
fac_pass
17
EXV A Maximum Steps Numb
1500/15000
12
1500
-
exva_max
18
EXV B Maximum Steps Numb
1500/15000
12
1500
-
exvb_max
19
Motor Cool. TQ Feedback
Yes/No
13
No
-
TQ_r_fbk
20
PD4 Aux Boards Select
Yes/No
14
No
-
pd4_aux
Parameters from 1 to 16 in version 1.x are the same than those in the new version 2.X.
For Retrofit from verson 1.x to the new 2.x, it is better to write down in a paper, configuration items
from 1 to 16. Use Service Tool to upload all the configuration from version 1 (example address 1).
Then use address search function to change the address to 2 before downloading the new software
version 2.x. Use Service Tool to add a new controller with a different addresse (example address 1 for
version 1 and address 2 for version 2). Once Upload configuration is done, fill factory configuration in
FACTORY table and then download this.
1.
1 = air cooled. 2 = water cooled . 3 = heat machine
2.
0 = no fan
< 4 = each DO output of the 4xDO board support 1 fan .
> 5 = DO # 1 and DO # 2 support 1 fan each.
DO # 3 support 2 fans
DO # 4 support 1 fan if circuit has 5 fans max
DO # 4 support 2 fans if circuit has 6 fans max
DO # 4 support 3 fans if circuit has 7 fans max
DO # 4 support 4 fans if circuit has 8 fans max
nb : these fans are not controlled by a varifan.
For pro_dialog 4 Auxiliary board select
, each DO output of the Auxiliary board support 1 fan
©
C
ARRIER
S
.
A
NOT
TO
BE
DISCLOSED
TO
PERSONS
OUTSIDE
CARRIER
ORGANIZATION
CARRIER SA
USER'S GUIDE FOR
30GX&HX PRO_DIALOG 4 V.2
ECG - UG - 02 - 02
Rev: Original
Page: 21 /98
Downloaded from
www.Manualslib.com
manuals search engine