Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
P174 CHECK LOW SPEED RPM
TRIGGER-ON speed was not within expected range during test or speed did not return to expected
range following transition back from high speed test.
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again or alarm may be manually reset via key-
pad or by turning the unit off then back on again.
1
Check microprocessor speed control and engine - refer to alarm 37
P175 CHECK HIGH SPEED RPM
TRIGGER-ON speed was not within expected range during test.
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again or alarm may be manually reset via key-
pad or by turning the unit off then back on again.
1
Check microprocessor speed control and engine - refer to alarm 38
P177 CHECK EVAPORATOR SUPERHEAT
TRIGGER-ON: Superheat control by the EVXV was not within the expected range during test.
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again or alarm may be manually reset via key-
pad or by turning the unit off then back on again.
1
Perform diagnostic testing and service of valve as required - refer to Section 8.5.4
P180 CHECK SUCTION MODULATING VALVE
TRIGGER-ON: Suction pressure control by the valve was not within the expected range during test.
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again or alarm may be manually reset via key-
pad or by turning the unit off then back on again.
1
Perform diagnostic testing and service of valve as required - refer to Section 8.6.7
P186 CHECK EVAPORATOR OUTLET TEMPERATURE
TRIGGER-ON: Sensor reading was not within the expected range during test.
UNIT CONTROL: Pretrip will fail and display "PRETRIP FAIL AND COMPLETED".
RESET CONDITION: Auto Reset if Pretrip is started again, or alarm may be manually reset via key-
pad or by turning the unit off, then back on again.
1
Check Sensor - refer to alarm 131
Содержание NDK33BN0KB
Страница 2: ......
Страница 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Страница 4: ......
Страница 14: ......
Страница 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Страница 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Страница 30: ...62 61753 21 2 6...
Страница 48: ......
Страница 212: ......
Страница 226: ......
Страница 248: ......
Страница 252: ......
Страница 262: ......
Страница 270: ......