62-61753-21
7-51
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
93
CHECK START UP BUZZER
TRIGGER-ON: The Buzzer circuit is shorted. (The Buzzer output from the microprocessor is negative,
so the circuit will not be shorted to ground, but is shorted either within the Buzzer itself, or to a posi-
tive wire.
UNIT CONTROL: Engine and standby operation: alarm only.
RESET CONDITION: Auto Reset when Buzzer amp draw is normal, or alarm may be manually reset
via keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Check Buzzer
a. Inspect Buzzer & wire connections. No damage to buzzer.
No damaged or corroded pins.
b. Check resistance of buzzer.
Refer to Section 2.12. Cannot be opened (infinite
ohms), shorted (Zero Ohms) or shorted to ground.
2
Check Buzzer Wiring
a. Inspect harness & control box
connector pins & terminals. (See
wiring schematic Section 10.)
No physical damage to harness.
No damaged or corroded pins.
3
Check Buzzer Current Draw
a. Use Component Test Mode to test
actual current draw of the circuit.
(Refer to Section 5.1.2.)
Component FET or board LED (refer to Table 5-1)
must be illuminated.
View current draw in Data List.
Refer to Section 2.12 for normal current values.
94
CHECK COMP CONTACTOR 1 (COMPRESSOR CONTACTOR RELAY)
TRIGGER-ON: Compressor Contactor Relay (CCONR) coil current is excessive.
UNIT CONTROL: Engine and standby operation: alarm only.
RESET CONDITION: Auto Reset or alarm may be manually reset via keypad or by turning the unit
off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Check CCONR
a. Inspect relay coil and terminals.
No damage to coil.
No damaged or corroded pins.
b. Check relay coil resistance.
Refer to Section 2.12. Cannot be opened (infinite
ohms), shorted (Zero Ohms) or shorted to ground.
2
Check CCONR Current Draw
a. Use Component Test Mode to test
actual current draw of the coil.
(Refer to Section 5.1.2.)
Component FET or board LED (refer to Table 5-1)
must be illuminated.
View current draw in Data List.
Refer to Section 2.12 for normal current values.
3
Check CCONR Wiring
a. Inspect harness & control box
connector pins & terminals. (See
wiring schematic Section 10.)
No physical damage to harness.
No damaged or corroded pins.
Содержание NDK33BN0KB
Страница 2: ......
Страница 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Страница 4: ......
Страница 14: ......
Страница 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Страница 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Страница 30: ...62 61753 21 2 6...
Страница 48: ......
Страница 212: ......
Страница 226: ......
Страница 248: ......
Страница 252: ......
Страница 262: ......
Страница 270: ......