62-61753-21
5-11
CONFIGURATION
SELECTIONS
DESCRIPTION
PM HOUR METER #1 (or 2 or 3 or 4
or 5) CONFIGURATION
OFF
ENGINE HOURS
SWITCH ON
HOURS
STANDBY HOURS
START CYCLES
HIGH SPEED
HOURS
OFF = The PM Maintenance Hour Meter is turned off.
ENGINE HOURS = PM Meter will monitor the number
of hours the engine has operated since the last reset.
SWITCH ON HOURS = PM Meter will monitor the
number of hours the unit has been switched on since
the last reset.
STANDBY HOURS = PM Meter will monitor the num-
ber of hours the unit has operated in standby since
the last reset.
START CYCLES = PM Meter will monitor the number
of times the unit has started since the last reset
HIGH SPEED HOURS = PM Meter will monitor the
number of hours the engine has operated in high
speed since the last reset.
PM HOUR METER #1 (or 2 or 3
or 4 or 5) RESET INTERVAL
Notes:
1. This Configuration will not dis-
play for those meters that are con-
figured OFF.
2. If the value entered is "0" the
meter will still count hours or cy-
cles as as configured but the
alarm feature for that meter is
turned off.
ENGINE HOURS
0 or
50 TO 30,000
hours in 50 hour
increments
SWITCH ON
HOURS
0 or
50 TO 30,000
hours in 50 hour
increments
STANDBY HOURS
0 or
50 TO hours in
50 hour increments
increments
START CYCLES 0
or
1,000 TO 90,000
CYCLES in 1,000
cycle increments
HIGH SPEED
HOURS
0 or
50 TO 30,000
hours in 50 hour
increments
The value to be entered here is the desired number of
hours or cycles between PM Maintenance Alarms for
this meter.
When the meter is reset, the value selected here will
be added to the to the present meter reading to indi-
cate to the controller when the next service interval
alarm will be triggered.
RANGE 1 LOCK
OR
RANGE 2 LOCK
(Applies to Compartment 1 only)
OFF
START-STOP
CONTINUOUS
OFF = If both Range Locks are OFF, the unit will
operate normally.
If either Range 1 or Range 2 is not OFF, the unit will
operate as selected whenever the setpoint is within
that range
START-STOP = The unit will always operate in Start-
Stop whenever the setpoint is between the minimum
& maximum temperatures for that range (see below).
CONTINUOUS = The unit will always operate in Con-
tinuous Run whenever the setpoint is between the
minimum & maximum temperatures for that range
(see the following sub-configurations).
RANGE 1 (or 2) MINIMUM
TEMPERATURE
-30°C to
32°C
(-22°F TO
89.6°F
)
in 0.1°F or °C in-
crements
Select the lowest temperature desired for this Range.
Содержание NDK33BN0KB
Страница 2: ......
Страница 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Страница 4: ......
Страница 14: ......
Страница 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Страница 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Страница 30: ...62 61753 21 2 6...
Страница 48: ......
Страница 212: ......
Страница 226: ......
Страница 248: ......
Страница 252: ......
Страница 262: ......
Страница 270: ......