C. Unit Start-Up
CWP STARTER HAS BEEN PROPERLY INTERLOCKED WITH THE CHILLER
ALL LIQUID VALVES ARE BACKSEATED
ALL DISCHARGE VALVES ARE OPEN
ALL SUCTION VALVES ARE OPEN, IF EQUIPPED
ALL OIL LINE VALVES ARE OPEN
UNIT HAS BEEN LEAK CHECKED
LOCATE, REPAIR, AND REPORT ANY REFRIGERANT LEAKS _____________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
CHECK VOLTAGE IMBALANCE:
AB ___________ AC __________ BC _____________
AVERAGE VOLTAGE
= _________________ (SEE INSTALLATION INSTRUCTIONS)
MAXIMUM DEVIATION
= _________________ (SEE INSTALLATION INSTRUCTIONS)
VOLTAGE IMBALANCE
= _________________ (SEE INSTALLATION INSTRUCTIONS)
VOLTAGE IMBALANCE IS LESS THAN 2%
DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%. CONTACT LOCAL POWER
COMPANY FOR ASSISTANCE.
ALL INCOMING POWER VOLTAGE IS WITHIN RATED VOLTAGE RANGE
CHECK COMPRESSOR RUNNING CURRENT:
CHECK COOLER WATER LOOP:
INLET PIPING TO COOLER INCLUDES A 20 MESH STRAINER
COOLER FLOW SWITCH SET FOR PROPER MINIMUM FLOW AND COOLER INTERLOCK ENABLED
WATER LOOP DESIGN VOLUME: __________________ GALLONS (LITERS)
CALCULATED VOLUME __________________GALLONS (LITERS)
3 GALLONS/NOMINAL TON (3.32 LITERS/kW) FOR AIR CONDITIONING
6 GALLONS/NOMINAL TON (6.65 LITERS/kW) FOR PROCESS COOLING
PROPER LOOP VOLUME ESTABLISHED
PROPER LOOP CORROSION INHIBITOR INCLUDED ____________GALLONS (LITERS) OF ___________
COMPRESSOR
NO LOADERS
ONE LOADER
FULL LOAD
COMP A1,L1
__________AMPS
__________AMPS
__________AMPS
COMP A1,L2
__________AMPS
__________AMPS
__________AMPS
COMP A1,L3
__________AMPS
__________AMPS
__________AMPS
COMP B1,L1
__________AMPS
__________AMPS
__________AMPS
COMP B1,L2
__________AMPS
__________AMPS
__________AMPS
COMP B1,L3
__________AMPS
__________AMPS
__________AMPS
COMP A2,L1
__________AMPS
__________AMPS
__________AMPS
COMP A2,L2
__________AMPS
__________AMPS
__________AMPS
COMP A2,L3
__________AMPS
__________AMPS
__________AMPS
COMP B2,L1
__________AMPS
__________AMPS
__________AMPS
COMP B2,L2
__________AMPS
__________AMPS
__________AMPS
COMP B2,L3
__________AMPS
__________AMPS
__________AMPS