Table 17 — Test Function and Subfunction Directory (cont)
Table 18 — Using Test Function
SUBFUNCTION
KEYPAD ENTRY
DISPLAY
COMMENT
3 Unit Discrete Outputs (cont)
Remote Alarm 2
Currently not supported.
Remote Alarm 3
Currently not supported.
Remote Alarm 4
Currently not supported.
Remote Alarm 5
Currently not supported.
Remote Alarm 6
Currently not supported.
Remote Alarm 7
Currently not supported.
Remote Alarm 8
Currently not supported.
Remote Alarm 9
Currently not supported.
Remote Alarm 10
Currently not supported.
Remote Alarm 11
Currently not supported.
Remote Alarm 12
Currently not supported.
Remote Alarm 13
Currently not supported.
Remote Alarm 14
Currently not supported.
Remote Alarm 15
Currently not supported.
Remote Alarm 16
Currently not supported.
4 Valves and Motormaster
Valves and Motor Master
Circuit A EXV Valve
Target Percent = 0%
Circuit A EXV Valve
Target Percent = 25%
Step in 25% increments.
Circuit A EXV Valve
Target Percent = 50%
Wait 30 seconds between each step for valve to
stop moving.
Circuit A EXV Valve
Target Percent = 75%
Valve may be closed in 25% increments by key-
ing in
. Wait 30 seconds between
each step for valve to stop moving.
Circuit A EXV Valve
Target Percent = 100%
Circuit B EXV Valve
Target Percent = 0%
Test same method as for Circuit A.
Circuit A Water Valve
Target Percent = 0%
Test same method as for EXV valves.
Circuit A% Fan Speed
Test same method as for EXV valves.
Circuit B% Fan Speed
Test same method as for EXV valves.
LEGEND
EXV
— Electronic Expansion Valve
KEYPAD ENTRY
DISPLAY RESPONSE
COMMENTS
Circuit A Discrete Output
Loader A1
Relay is OFF
Appears on screen momentarily, then will switch to Loader A1.
Loader A1
Relay is ON
Compressor Loader A1 solenoid energized
Loader A1
Relay is OFF
Compressor Loader A1 solenoid deenergized
Valves and Motor Master
Circuit A EXV Valve
Target Percent = 0%
Circuit A EXV Valve
Target Percent = 25%
Continue pressing
to step to 50%, 75%, and 100%.
Wait 30 seconds between each step for valve to stop moving.
Circuit A EXV Valve
Target Percent = 0
Continue pressing
to step closed.
LEGEND
EXV
— Electronic Expansion Valve
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER