CL-5
PERFORM TEST FUNCTION (INDICATE POSITIVE RESULT):
ONCE POWER IS SUPPLIED TO THE UNIT, CHECK THE DISPLAY FOR ANY ALARMS, SUCH AS PHASE REVERSAL.
FOLLOW THE TEST FUNCTION INSTRUCTIONS IN THE CONTROLS AND TROUBLESHOOTING LITERATURE. BE
SURE TO CHECK FOR PROPER FAN ROTATION WITH THE FAN TEST SECTIONS. BE SURE ALL SERVICE VALVES
ARE OPEN BEFORE BEGINNING THE COMPRESSOR TEST SECTION. ITEMS MARKED WITH “†” CAN BE TESTED
ONLY IF THE UNIT IS CONFIGURED FOR THIS OPTION. DO NOT RUN OIL PUMPS FOR MORE THAN 20 SECONDS.
CHECK FOR COMMUNICATING MODULES (BLINKING RED AND GREED LEDs)
CORRECT FLUID SET POINTS ARE ENTERED
COOL SET POINT 1 _____________
COOL SET POINT 2 _____________
CORRECT DATE, TIME, AND OPERATING SCHEDULE(S) ARE SET
LOADER A1
LOADER B1
LOADER A2
LOADER B2
MINIMUM LOAD VALVE A†
MINIMUM LOAD VALVE B†
CIRCUIT A OIL HEATER
CIRCUIT B OIL HEATER
A1 MOTOR COOLING SOLENOID
B1 MOTOR COOLING SOLENOID
A2 MOTOR COOLING SOLENOID†
B2 MOTOR COOLING SOLENOID†
CIRCUIT A OIL PUMP
CIRCUIT B OIL PUMP
OIL SOLENOID A1
OIL SOLENOID B1
OIL SOLENOID A2†
OIL SOLENOID B2†
CIRCUIT A EXV
FAN 1 (30GX)†
CIRCUIT B EXV
FAN 2 (30GX)†
CIRCUIT A WATER VALVE†
FAN 3 (30GX)†
CIRCUIT A% FAN SPEED (GX)†
FAN 4 (30GX)†
CIRCUIT B% FAN SPEED (GX)†
FAN 5 (30GX)†
FAN 6 (30GX)†
COOLER PUMP†
COMPRESSOR A1
CONDENSER PUMP†
COMPRESSOR A2†
COOLER HEATER†
COMPRESSOR B1
ALARM RELAY†
COMPRESSOR B2†