ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
64
Technician Settings P189 to P195
P189 – Dehumidification cycle in unoccupied mode
Range: 0...600 minutes
Default: 20 minutes
P190 – Dehumidification break time in unoccupied mode
Range: 0...900 minutes
Default: 40 minutes
P192 – Temperature setpoint for reheat in unoccupied mode
Range: 10...30ºC / 50...86ºF
Default: 15ºC / 59ºF
P193 – Display switching time (between temperature and humidity)
Range: 0...11 seconds
Default: 5 seconds
P194 – Humidity differential band
Range: 0...10 %RH
Default: 5%RH
P195 – Humidity sensor reading offset
Range: -9…+9 %RH
Default: 0 %RH