ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
63
Technician Settings P122 to P188
P122 – Cool Proportional output threshold time (seconds) (FC only)
Range: 0...100 seconds
Default: 60 seconds
P123 – Heat Proportional output threshold time (seconds) (FC Only)
Range: 0...100 seconds
Default: 60 seconds
P160 – Minimum compressor ON time (AC only)
Range: 0...20 minutes
Default: 2 minutes
P161 – Minimum compressor OFF time (AC only)
Range: 0...20 minutes
Default: 13 minutes
P170 – Economizer low limit temperature
Range: 9...27ºC / 48...80ºF
Default: 17ºC / 63ºF
P187 – Display or hide humidity reading
“00” - Do not display humidity reading
“01” - Display humidity reading
P188 – Room temperature limit for disabling dehumidification in
unoccupied mode
Range: 10...30ºC / 50...85ºF
Default: 18ºC / 64ºF