To set up the driver
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
48
All rights reserved
Calendars
Calendars are provided in the driver for BACnet compatibility only. Instead, use the
Schedules
feature in the i-Vu®
interface.
Common and Specific Alarms
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
Common alarms:
Specific alarm:
•
Module Halted
•
All Programs Stopped
•
Duplicate Address
•
Locked I/O
•
Control Program
•
Program Stopped
•
Excessive COV
•
Dead Module Timeout
•
Low Battery Alarm
NOTE
To set up alarm actions for controller generated alarms, see "Setting up alarm actions" in i-Vu® Help.
Module Generated Alarm
Description
Short message shown on the
Alarms
page or in an alarm action when this type of
alarm is generated.
Events
Alarm Category and Alarm
Template
See "Alarms" in i-Vu® Help.
Enable
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from this controller.
Notification Class
Do not change this field.
Custom Translation Tables
You can set up a translation table that an analog input will use to translate the raw data from a non-linear sensor
to the engineering units you want it to output on the wire. In the navigation tree, select
Custom Translation Table
#1
,
#2
, or
#3
. The
Properties
page has instructions. For the input to use the translation table, navigate to the
input, select the
Details
tab, then set
Sensor Type (Scaling Method)
to
Non-Linear, Custom Table #__
.