Adding the Carrier® ChillerVu™ into the i-Vu® or Field Assistant system
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
33
All rights reserved
The following instructions assume that you have already installed the i-Vu® and Field Assistant application.
If the Carrier® ChillerVu™ is a CCN Gateway (the default), you must first find and upload it as an Open controller in
the i-Vu® interface.
NOTE
If the Carrier® ChillerVu™ is used on a CCN network, you cannot use Field Assistant to find CCN equipment or download CCN applications.
You MUST use the i-Vu® application.
To prepare to create your system
You must create the control program before building your Carrier® ChillerVu™ system.
The Carrier® ChillerVu™ accepts any of the following:
○
Applications from the psm (plant system manager) equipment SAL library
NOTE
These applications will not load into any controller except the Carrier® ChillerVu™ controller.
○
UC applications from the Universal Controller equipment sal library
○
Air Handler applications from the AHU Builder library
○
CCN applications from the ivu-6.0 or 6.5-discovery library
○
User-created Snap programs
NOTE
When creating your program in the Snap interface, you must select
Control Program
>
PSM
,
Open
(non PIC)
, or
CCN
to be able to download the program into the controller.
The EquipmentBuilder or Snap application
1
Use the EquipmentBuilder or Snap application to create control program(s) for your Carrier® ChillerVu™.
2
If applicable, print the Sequence of Operation, which includes the points list.
NOTE
You can create a points list under
Reports
in the i-Vu® application.
This Installation Guide
1
Prepare a wire list. See the
Appendix
(page 63).
2
Use the wire list to install and wire I/O points to your Carrier® ChillerVu™ and expanders, if applicable.
Adding the Carrier® ChillerVu™ into the i-Vu® or Field Assistant system