Adding the Carrier® ChillerVu™ into the i-Vu® or Field Assistant system
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
38
All rights reserved
4
Under
Driver
, expand
Protocols
>
LonWorks
.
5
Select
Port S2 is connected to the LonWorks network
.
6
Select
Option Card
.
7
Set
Baud
to 38.4 kbps.
NOTE
This is the the baud rate between the LonWorks Option Card and the Carrier® ChillerVu™, not the
LonWorks network.
8
Select
Explicit
for
Addressing Mode
.
9
Accept all other default settings.
10
Click
Accept
.
LonWorks network using the SLTA-10
1
Verify the
Port S2
DIP switch (5)
TPI
is
On
and the controller's power has been cycled.
2
In the i-Vu® navigation tree, right-click the Carrier® ChillerVu™ and select
Driver Properties
from the drop-
down menu.
3
Under
Driver
, expand
Protocols
>
Lonworks
.
4
Under
Port Configuration
, select
Port S2
for
is connected to the LonWorks network
, then select
SLTA
.
5
Set
Baud
to 57.6 kpbs.
NOTE
This is the the baud rate between the LonWorks SLTA-10 and the Carrier® ChillerVu™, not the
LonWorks network.
6
Accept all other default settings.
7
Click
Accept
.