Table 18 — UPS
Main Menu
Configuration Menu
UPS [Table CFG_UPS]
Table 19 — Config Metering
Main Menu
Configuration Menu
Config Metering [CFGMETER]
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
UPS Option
Disable/Enable
NA
Enable
1
Battery Replacement Done
No/Yes
Yes
Battery Threshold
0 to 100
%
70
60
Battery Minimum Runtime
0 to 600
sec
240
240
Battery Test Duration
0 to 600
sec
240
240
Power Failure Max Number
0 to 100
10
5
Over Temp Duration
0 to 600
sec
60
60
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Cond Liquid Level Determination
0=Capacity Percent, 1=Setpoint
0 to 1
0
Liquid level SP-Cap 0%
%
0.5
0.5
Liquid level SP-Cap 25%
%
1.0
1.0
Liquid level SP-Cap 50%
%
1.5
1.5
Liquid level SP- Cap 75%
%
2.0
2.0
Liquid level SP- Cap 100%
%
2.1
2.1
Low SST Set Point
°F
34
34
Eco EXV Option
Disable/Enable
Enable
Eco EXV Active Threshold
%
0
Eco Superheat SP
^F
10
EXCSV Option
Disable/Enable
Enable
EXCSV Activate Threshold
%
95
95
EXCSV Deactivate Threshold
%
15
15
EXCSV Open Time
sec
60
60
EXCXV Close Time
sec
120
120
EXCSV Open Step
5
5
EXCSV Close Step
5
5