MODIFY CONTROLLER IDENTIFICATION IF NECESSARY
The CCN address can be changed from the Configuration Menu.
Change this address under CONTROL IDENTIFICATION for
each chiller if there is more than one chiller at the jobsite. Write
the new address on the PIC6 Touch Screen module for future
reference.
CONFIGURE TABLES
Access the related tables through MAIN MENU CONFIGURA-
TION MENU (Fig. 25) to modify or view job site parameters
shown in 19MV Configuration tables. Tables 10-19 should be
verified or configured during startup/commissioning. Consult
chiller nameplates as indicated. Tables 10-19 include typical pa-
rameters; for the complete list of parameters, consult the Initial
Start-up Checklist in this manual or 19MV Controls Operation
and Troubleshooting Manual.
Table 11 — MBC Configuration
Main Menu
Configuration Menu
MBC Configuration
Table 12 — Service Parameters Table
Menu
Configuration Menu
Service Parameters [SERVICE1]
* Most Service Parameters do not require any change from default.
Adjust as required.
Table 13 — Surge Correction Config
Menu
Configuration Menu
Surge Correction
Table 10 — Factory Parameters
DESCRIPTION
RANGE
DEFAULT
VALUE
Chiller type
0 to 4
0
4=19MV
Lubrication type
0 to 2
0
2=Mag Bearing
VFD/Starter Option
0 to 9
0
job specific
Unit Type
0 to 1
0
0=Cool Only
Refrig type
0 to 2
0
job specific
Chilled Medium Type
0 to 1
0
0
Cond Shell Side MAWP
0 to 1
0
0=185 psi
Country Code
0 to 999
86
01
Activate Swift Rst Opt
Yes/No
No
No
Activate Freq Start Opt
Yes/No
Yes
Yes
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Calibration on Powerup
Disable/Enable
Disable
Disable
Auto Clearance Check
Disable/Enable
Enable
Enable
Clearance Fail Criteria
0 to 100
%
7.5
7.5
Auto Levitation
Yes/No
Yes
Yes
Shutdown de-Levi delay
60 to 600
sec
60
60
Speed Signal Alarm Delta
0 to 50
%
10
10
Speed Signal Alert Delta
0 to 20
%
5
5
Shaft Displacement Limit
4 to 10
mils
6.0
6.0
Speed Sensor Option
Yes/No
Enable
Enable
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE*
Atmospheric Pressure
8 to 15
PSI
14.5
job specific
IGV2 Deg @ IGV1 20 Deg
10 to 40
deg
37
37
IGV2 Deg @ IGV1 30 Deg
10 t0 50
deg
45
45
GV2 Deg @ IGV 50 Deg
10 to 80
deg
67
67
Enable Excessive Starts
0 to 1
NA
No
job specific
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Surge Line Configuration
0 to 2
NA
0
2=PR Table
Surge Profile Step
0 to 2
^F
0
0
Surge Profile Offset
0 to 5
^F
0
0