19MV PIC6 CFGUMVFDUM VFD CONFIGURATION TABLE CONFIGURATION SHEET
19MV PIC6 GENCONF - General CONFIG TABLE CONFIGURATION SHEET
19MV PIC6 CFGGEVFD_GENERAL VFD CONFIG TABLE CONFIGURATION SHEET
19MV PIC6 RESETCFG - Temperature Reset CONFIG TABLE CONFIGURATION SHEET
19MV PIC6 CFG_UPS - UPS CONFIG TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Compressor Speed 100%
47 to 450
Hz
50
Rated Line Voltage
200 to 13800
Volts
460
Motor Nameplate Current
10 to 2000
AMPS
200
Motor Rated Load Current
10 to 2000
AMPS
200
Motor Nameplate RPM
0 to 15000
rpm
3000
Motor Rated Torque (NM)
0.1 to 10000
NM
200
Motor Nameplate KW
0 to 5600
kW
1500
Increase Ramp Time
5 to 120
sec
30
Decrease Ramp Time
5 to 60
sec
30
Switch Frequency (kHz)
0 to 16
kHz
5
PM Motor Para Download
Disable/Enable
Disable
Stator Resistance (Rs)
0.0010 to 140
Ohm
0.0010
d-axis Inductance (Ld)
0 to 1000
Henry
0.010
q-axis Inductance (Lq)
0 to 1000
Henry
0.010
Back EMF at 1000 RPM
1 to 9000
V
10
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Stop to Start Delay
0 to 15
min
1
Start to Start Delay
0 to 45
min
1
Demand Limit Type
0=Base Demand, 1=4 to 20mA
0 to 1
0
Pulldown Ramp Type
0=Temp, 1=Load
0 to 1
1
Demand Limit Source
0=Amps, 1=KW
0 to 1
0
Reboot PIC6
No/Yes
No
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
VFD Gain
0.1 to 1.5
0.75
VFD Max Speed Per
90 to110
%
100
VFD Min Speed Per
65 to 89
%
70
VFD Start Speed Per
45 to 100
%
100
VFD Current Limit
0 to 99999
AMPS
250
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Temp Reset Type
0=No, 1=4 to 20mA,
2=Remote Temp, 3=Water DT
0 to 3
0
Degrees Reset at 20mA
–30 to 30
^F
10
Maximum Deg Temp Reset
–30 to 30
^F
10
Remote Temp Full Reset
–40 to 245
^F
65
Remote Temp No Reset
–40 to 245
^F
85
Deg Reset Water DT Full
–30 to 30
^F
10
Controlled DT Full Reset
0 to 15
^F
0
Controlled DT No Reset
0 to 15
^F
10
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
UPS Option
Disable/Enable
Disable
Battery Replace Done
No/Yes
Yes
Battery Threshold
0 to 100
%
70
Battery Minimum Runtime
0 to 600
sec
240
Battery Test Duration
0 to 600
sec
240
Power Failure Max Number
0 to 100
%
50
Over Temp Duration
0 to 600
sec
60