19MV PIC6 FACTORY TABLE CONFIGURATION SHEET
19MV PIC6 MBC CONFIGURATION TABLE CONFIGURATION SHEET
19MV PIC6 SERVICE PARAMETERS CONFIGURATION TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Chiller Type
19XR6/7=0,19XR2~E/D/V=1,
19DV=2, 19XRF=3, 19MV=4
0 to 4
4
Lubrication Type
Mag Bearing=2
2
VFD/Starter Option
Danfoss VFD=7
7
Unit Type
Cooler Only=0
0
Ref Type
R-134a=0, R-513A=1
0
Chilled Medium Type
Water/Brine
Water
Cond Shell Side MAWP
0=185 psi, 1=300 psi
0 to 1
psig
0
Country Code
0 to 999
01
Activate Swift Rst Opt
No/Yes
No
Activate Freq Start Opt
No/Yes
Yes
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Calibration on Power Up
Disable/Enable
Enable
Auto Clearance Check
Disable/Enable
Enable
Clearance Chk on Powerup
Disable/Enable
Enable
Clearance Fail Criteria
0 to 100
%
7.5
Auto Levitation
No/Yes
Yes
Shutdown de-Levi delay
60 to 600
sec
60
Speed Signal Alarm Delta
0 to 50
%
10
Speed Signal Alert Delta
0 to 20
%
5
Shaft Displacement Limit
4 to 10
mils
6
Speed Sensor Option
Disable/Enable
Enable
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Atmospheric Pressure
8 to 15
psi
14.5
GV1 Travel Limit
30 to 100
%
93.6
GV1 Closure at Startup
0 to 4
4
%
IGV2 Travel Limit
30 to 100
%
93.6
IGV2 Minimum Degree
0 to 20
Deg.
2.0
IGV2 Full Load Open Degree
10 to 100
Deg.
88.0
IGV2 Actuator Max Deg
90 to 120
Deg.
94.0
IGV2 Position @IGV1 20°
10 to 40
Deg.
37.0
IGV2 Position @IGV1 30°
10 to 50
Deg.
45.0
IGV2 Position @IGV1 50°
10 to 80
Deg.
67.0
Maximum GV Movement
1 to 4
%
2
Controlled Fluid DB
0.5 to 2
^F
1
Derivated EWT Gain
1 to 3
2
Proportional Dec Band
2 to 10
6
Proportional Inc Band
2 to 10
6.5
Demand Limit at 20 mA
10 to 100
%
40
Demand Limit Prop Band
3 to 15
%
10
Amps or KW Ramp per Min
5 to 20
%
5
Temp Ramp per Min
1 to 10
^F
3
Recycle Shutdown Delta T
0.5 to 4
^F
1
Recycle Restart Delta T
2 to 10
^F
5
Water Flow Verify Time
0.5 to 5
min
5
Enable Excessive Starts
No/Yes
No