Table 38 —
Air Handler VFD Factory-Set Parameters
GROUP
NUMBER
PARAMETER
NUMBER
DESCRIPTION
VFD DRIVE ONLY
PARAMETERS
VFD WITH E-CLIPSE DESCRIPTION /
PARAMETER
99
9902
Application Macro
Supply Fan
Eclipse
HVAC / 9902
9904
Motor Control Mode
Scalar
Scalar
9905
Motor Normal Voltage
*
*
9906
Motor Normal Current
†
†
9907
Motor Normal Frequency
60hz or 50hz
60hz or 50hz
9908
Motor Normal Speed
Name plate rpm at load
Name plate rpm at load
9909
Motor Normal Power
Nameplate Hp
Nameplate Hp
10
1001
EXT 1 Commands
DI-1 / 1001 (Start/Stop)
COMM
DI-1 / 1601
1002
EXT 2 Commands
(0) N/A
COMM
1003
Direction
Forward
Forward
11
1104
REF 1 Minimum
9.33 Hz at 60 Hz/ 7.78 Hz 50 Hz 9.33 Hz at 60 Hz/ 7.78 Hz 50 Hz
1105
REF 1 Maximum
Belt Drive 60Hz/50Hz Direct
Drive Calculated Per Fan and
Motor
Belt Drive 60Hz/50Hz Direct
Drive Calculated Per Fan and
Motor
12
1201
Constant Speed Select
DI-3
NOT SEL
1202
Constant Speed Value
Field Program
(8Hz - Motor Nominal Freq.)
Field Program
(8Hz - Motor Nominal Freq.)
13
1301
Minimum AI-1
0%
0%
1302
Maximum AI-1
100%
100%
1303
Filter AI-1
1 sec.
1 sec.
1304
Minimum AI-2
0%
0%
1305
Maximum AI-2
100%
100%
1306
Filter Ai-2
1 sec.
1 sec.
14
1401
Relay Output 1
Started
READY
1402
Relay Output 2
Run
Run
1403
Relay Output 3
Fault (inverted)
Fault (inverted)
16
1601
Run Enable
DI-2 / 1601
EMS S/S (Field Installed)
DI-2 / 1602
1608
Start Enable 1 (safety 1)
DI-4 / 1608
Safety (COMM)
DI-3 / 1603
1609
Start Enable 2 (safety 2)
DI-5 / 1609
Safety (Not configured)
DI-4 / 1604
20
2002
Maximum Fan Speed
Per Fan
Per Fan
2003
Maximum Current
**
**
2007
Minimum Frequency
8Hz
8Hz
2008
Maximum Frequency
Belt Drive 60Hz/50Hz Direct
Drive Calculated Per Fan and
Motor
Belt Drive 60Hz/50Hz Direct
Drive Calculated Per Fan and
Motor
21
2101
Start Function
Fly Start
Fly Start
2102
Stop Function
Coast
Coast
22
2202
Acceleration Time
60 Seconds
60 Seconds
2203
Deceleration Time
60 Seconds
60 Seconds
26
2605
Volt/Freq Ratio
Linear
Linear
2606
Switching Frequency
8 hz
8 hz
2607
Switching Frequency Con-
trol
ON
ON
30
3006
Motor Thermal Time
1050
1050
3007
Motor Load Curve
105%
105%
3008
Zero Speed Load
70%
70%
3009
Break Point Frequency
35 Hz
35 Hz
3010
Stall Function
Fault
Fault
3011
Stall Frequency
20 Hz
20 Hz
3012
Stall Time
20 Sec.
20 Sec.
3017
Earth Fault
Fault
Fault