![Carrier Aero 39MN Series Скачать руководство пользователя страница 117](http://html1.mh-extra.com/html/carrier/aero-39mn-series/aero-39mn-series_installation-start-up-and-service-instructions-manual_2562126117.webp)
117
8. Remove the unit lifting lugs under the coil section that match
the CCH side walls. DO NOT REMOVE THE LIFTING
LUG BOLTS AS THEY WILL BE USED TO ATTACH
THE ANGLE.
9. If the CCH has no door, remove the side panels before pro
-
ceeding with the installation.
10. a. Using the lifting brackets (shown in Fig. 67), lift the
CCH into the vertical position and remove the ship
-
ping brackets (shown in Fig. 61).
b. Using the lifting brackets (shown in Fig. 67) place the
CCH on top of the CCH curb. Once in position there
should be about a 2-in. gap between the unit wall and
the CCH frame covered by the flashing.
11. Attach the angle bracket using the lifting lug nuts and wash
-
ers; do not fully tighten. DO NOT USE THIS PART FOR
LIFTING THE UNIT. See Fig. 67, Detail A.
12. Place the filler plate inside the CCH baserail, align the square
holes with the pattern on the base rail and the angle bracket,
then insert the 3 carriage bolts provided through the plate,
base rail and angle bracket. Fully tighten with provided wash
-
ers and nuts. See Fig. 67, Detail A.
13. Finish tightening the angle bracket to the unit base rail. See
Fig. 67, Detail A.
14. Screw cover top to drain channel. See Fig. 68.
15. Place the slider onto drain channel-CCH roof cap tabs. Bend
or crimp both ends of slider to lock the part in place. See
Fig. 69.
16. Reassemble panels.
17. Attach the side flashing to the CCH frame using
1
/
4
in. —14 x
3
/
4
in. long screws provided.
18. Caulk all notches and gaps as shown Fig. 70.
Fig. 67 —
Positioning CCH
Fig. 68 —
Screwing CCH Roof to Drain Channel
Fig. 69 —
Side View
Fig. 70 —
Sealing Gaps
ANGLE
BRACKET
FILLER
PLATE
CARRIAGE
BOLTS
SEE DETAIL A
DETAIL A
LIFTING
BRACKETS
LEGEND
CCH
—
Coil Connection Housing
SEAL
DRAIN CHANNEL
AHU ROOF
ROOF RAIL
SEAL
SIDE FLASHING
CCH PANEL
SEAL
CCH ROOF
BRACKET SLIDER
BEND AND CRIMP
FINAL ENDS
SEAL GAPS BETWEEN
SIDE FLASHING, DRAIN
CHANNEL, CCH CAP
AND FRAME
TO ALLOW FOR
DRAINAGE, DO NOT
CAULK THIS AREA
DOUBLE
FACE TAPE
LEGEND
AHU
—
Air-Handling Unit
CCH
—
Coil Connection Housing
AHU
CCH
CCH CURB
SEAL GAPS
WOOD
NAILER
LEGEND
AHU
—
Air-Handling Unit
CCH
—
Coil Connection Housing