142
2. Remove the appropriate size knockout using a suitable
knockout punch tool. Do NOT use a drill; metal shavings
will damage the drive.
3. Connect the field-supplied conduit to the VFD enclosure.
4. Refer to the wiring diagram supplied with the VFD
connect the line voltage power source to the line voltage
terminals (U1, V1, W1) as shown.
5. Refer to the factory-supplied voltage warning label and
verify that the power source is correct.
6. Connect the ground wire to the grounding lug provided
on the bottom of the VFD.
7. Select another suitable location on the bottom of the VFD
to connect the field-supplied control wiring.
8. Locate and use one of the unused knockouts on the VFD
housing and connect the control wiring conduit. Refer to
Fig. 118 and 119 for field control wiring connections.
NOTE: If a 0 to 10 or 2 to 10 vdc signal is used to control the
drive speed, reset the dipswitch to the voltage or V position.
Verify that the AI switch is set to the voltage position. See
Fig. 121. DO NOT reprogram the drive.
START-UP AND TEST
1. Close and secure the fan access door and the VFD cover.
2. Apply power and allow drive to initialize.
3. If fan is a direct drive type, then ensure VFD has been
programmed with the correct values for parameters 2002
and 2008 to maximum fan speed and maximum VFD out
-
put frequency to limit motor speed to the fan maximum.
4. Verify max fan rpm from label on fan sled.
5. Verify motor Hz and nominal operating speed on motor
nameplate.
6. Calculate the maximum frequency output from the VFD.
Maximum frequency = motor frequency (Hz) * fan maxi
-
mum speed (rpm) ÷ motor nominal operating speed
(rpm).
7. Verify that parameter 2002 (maximum fan speed) has
been set to match value on the fan label.
8. Select MENU to enter the main menu.
9. Select CHANGED PAR with the UP/DOWN buttons and
select ENTER.
10. Select parameter 2002 and verify it equals the maximum
fan speed.
11. If values are equal, then go to Step 14.
12. If values are not equal, select EDIT, press the UP/DOWN
buttons to match the required value.
13. Select SAVE to store the modified value.
14. Select EXIT to return to the listing of parameters.
15. Select Parameter 2008 and verify it equals the maximum
VFD output frequency.
16. If values are equal, then go to Step 19.
17. If values are not equal, select EDIT, press the UP/DOWN
buttons to match the required value.
18. Select SAVE to store the modified value.
19. Select EXIT to return to the listing of parameters.
20. Select EXIT to return to the main menu.
21. Press the HAND button and verify that the drive operates
at 8 Hz.
22. Press Up arrow to increase speed and Down arrow to de
-
crease speed.
23. Press the Off button and verify that the fan stops.
24. Press the Auto button to operate the drive from the Ener
-
gy Management System (EMS) interface. Verify that all
VFD interface functions are working (start/stop, speed
controls, fire/smoke, shutdown, etc.) between the VFD
and the EMS.
Refer to Tables 37 and 38 for additional VFD information.
VFD with Bypass
When the VFD and bypass are factory-installed, they are wired to
the motor and fully tested before shipped. The VFD is pro
-
grammed at the factory as ordered, including electronic overload,
which is programmed for the motor FLA (full load amps) as sup
-
plied.
Open the bypass box cover and the fan section access door to
check for any damage before proceeding.
CAUTION
Failure to ensure parameters 2002 and 2008 are correct can
result in damage to the fan wheel.