37
9.3 - Flow control
9.3.1 - Evaporator flow switch and chilled water pump
interlock
NOTE: This is obligatory and 30HXC units:
•
The unit water flow switch must be energised.
• The chilled water pump start-up interlock must be
connected.
Failure to follow this instruction will void the Carrier guarantee.
The flow switch is supplied, installed on the evaporator entering
water pipe and preset at the factory to cut out when there is
insufficient water flow.
If any adjustment is required, please refer to chapters:
•
9.3.1.1 for the more recent flow switches,
•
9.3.1.2 for older flow switches (orange colour).
9.3.1.1 - Flow switch - reference number 00PPG000472900A
IMPORTANT: To adjust the setpoint the unit must be energised,
but without water flow.
The default control point is 60 cm/s (0.6 m/s) for all applications.
For option 6 the factory setting is 10 cm/s (0.1 m/s).
Changing the setpoint is only necessary if glycol is used in the
water system (positive brine), and the correct value is 10 cm/s
(0.1 m/s).
If adjustment is required,
the push button below must always be
used for safe adjustment. This is available from the Carrier
spare parts department
.
•
Switch on the unit without water flow.
•
Disconnect the flow switch connector and insert the push
button in series with the flow switch.
•
Follow sequence A to F below.
NOTE: The new setpoint (in cm/s) corresponds to the duration
(in seconds) the push button is pressed.
Control sequence
Timing Operation
A
Initialisation:
Press the push button for longer than 1 second
B
Initialisation validation:
Release the button for between 1 and 5
seconds
C
Threshold control:
Press for the number of seconds that corresponds to
the required setpoint (pressing for 10 seconds sets the setpoint to 10 cm/s
or 0.1 m/s)
D
Release for 5 seconds
E
Stored information feedback:
The light is on for the number of seconds
that corresponds to the setpoint.
F
Internal control:
The flow switch goes out for 5 seconds and can then
be disconnected from the push button.
Timing
A
B
C
D
E
F
Duration, s
> 1
1 to 5
3 to 67
5
5 to 65
5
Do not forget to remove the push button at the end of the operation
and replace the connector on the flow switch.
9.3.1.2 - Flow switch - ref. No. HR12AA009EE (orange colour)
If adjustment is necessary:
1. Switch on the unit. Set it to constant flow (preset value).The
yellow LED is illuminated, and the output is switched for
approximately 20 seconds (power-on delay time).
2. Turn the potentiometer until only one green LED is
illuminated. The further the green LED is from the yellow
LED, the safer the adjustment (standby capacity in case of
flow or temperature fluctuations).
3. After the adjustment attach the label supplied to the
potentiometer, in order to protect it against unauthorised
tampering.
Terminals 34 and 35 are provided for field installation of the
chilled water pump interlock (auxiliary contact for pump operation
to be wired on site).
Potentiometer adjustment (ref.: HR12AA009EE)
Legend
1 Setting potentiometer sensitivity
2 Chain of LEDs
- red LED lights: the unit is not adjusted
- yellow LED lights: the output is switched
- green LED lights: the unit is adjusted
2
1
Push button
Flow switch
ref. No. 00PPG00473000A
ref. No. 00PPG000472900A