18
5.2 - Electrical data - 30HXC + option 60
30HXC
080 090
100 110 120 130 140 155 175
190
200 230 260
285
310 345 375
Power circuit
Nominal power supply (Un)*
V-ph-Hz 460-3-60
Voltage range
V
414-506
Control circuit supply
The control circuit is supplied via the factory-installed transformer
Nominal operating power input*
kW
56
63
69
78
82
91
103
111
123
129
142
166
189
198
223
249
261
Nominal operating current drawn*
A
94
101
109
121 133
147
164
178
194
213
228
260
291 319
355
388 425
Total harmonic distortion***
%
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Max. operating power input**
kW
87
96
105
118
130
144
159
172
187
212
223
253
281
318
344
374
424
Circuit A**
kW
-
-
-
-
-
-
-
-
-
-
144
159
187
212
172 187
212
Circuit B**
kW
-
-
-
-
-
-
-
-
-
-
79
94
94
106
172 187
212
Max. operating current drawn
(Un - 10%)***
A
134
147
161
180 200
220
243
263
286
324
340
386
429
486
526
572
648
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
220
243
286
324
263
286 324
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
120
143
143
162 263
286 324
Maximum operating current drawn
(Un)***
A
122 134 146
164
182
200
221
239
260
294
309
351
390
441
478
520 588
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
200
221
260
294
239
260
294
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
109
130
130
147
239
260
294
Maximum starting current,
standard unit (Un)
†
A
165
165
177
201
195
244
274 292
313 363
685
801
840
979
928
970
1126
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
576
671
710
832
689
710
832
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
485
580
580
685
689
710
832
Max. starting current/max. current
draw ratio, unit
1,35 1,23 1,21 1,23
1,19
1,22 1,24 1,22 1,20 1,23 2,22 2,28 2,15 2,22
1,94 1,87 1,91
Max. starting current/max. current
draw ratio, circuit A
-
-
-
-
-
-
-
-
-
-
2,88 3,04
2,73
2,83 2,88
2,73
2,83
Max. starting current/max. current
draw ratio, circuit B
-
-
-
-
-
-
-
-
-
4,45 4,46 4,46 4,66 2,88
2,73
2,83
Max. starting current - reduced
current start (Un)
†
A
std
std
std
std
std
std
std
std
std
std
550
621
660
714
748
790
861
Circuit A
A
-
-
-
-
-
-
-
-
-
-
441
491
530
567
509
530
567
Circuit B
A
-
-
-
-
-
-
-
-
-
-
260
330
330
370
509
530
567
Max. starting current - red. current
start/max. current draw ratio, unit
std
std
std
std
std
std
std
std
std
std
1,78 1,77 1,69
1,62 1,56 1,52 1,46
Circuit A
-
-
-
-
-
-
-
-
-
-
2,21 2,22 2,04
1,93
2,13 2,04
1,93
Circuit B
-
-
-
-
-
-
-
-
-
-
2,39
2,54 2,54 2,52 2,13 2,04
1,93
Three-phase short circuit holding
current
kA
25
25
25
25
25
25
25
25
25
25
N/A N/A N/A N/A N/A N/A N/A
Circuit A
kA
-
-
-
-
-
-
-
-
-
-
25
25
25
25
25
25
25
Circuit B
kA
-
-
-
-
-
-
-
-
-
-
15
15
15
15
25
25
25
Customer standby capacity, unit
or circuit B, for evaporator water
pump connections
‡
kW
8
8
8
11
11
11
15
15
15
15
15
18
18
30
30
30
30
* Based on standardised ARI conditions: Evaporator entering/leaving water temperature 12.2°C and 6.7°C. Condenser entering/leaving water temperature 29.6°C/35°C.
** Power input, compressor, at unit operating limits (evaporator water entering/leaving temperature = 15°C/10°C, condenser entering/leaving water temperature =
45°C/50°C) and a nominal voltage of 460 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
†
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor)
‡
Current and power inputs not included in the values above.
N/A Not applicable