32
8.4.2 - Selection table of minimum and maximum wire sections - 400 V-3 ph-50 Hz
30HXC
Minimum wire
section (mm2)*
Wire type
L (m)
Maximum wire
section (mm2)*
Wire type
L (m)
080
1 x 50
XLPE Cu
160
1 x 120
XLPE Al
205
090
1 x 50
XLPE Cu
160
1 x 120
XLPE Al
205
100
1 x 70
XLPE Cu
170
1 x 150
XLPE Al
210
110
1 x 70
XLPE Cu
170
1 x 185
XLPE Al
220
120
1 x 95
XLPE Cu
180
1 x 185
XLPE Al
220
130
1 x 95
XLPE Cu
180
1 x 240
XLPE Al
225
140
1 x 120
XLPE Cu
185
2 x 95
XLPE Al
195
155
1 x 120
XLPE Cu
185
2 x 120
XLPE Al
205
175
1 x 150
XLPE Cu
190
2 x 120
XLPE Al
205
190
1 x 185
XLPE Cu
190
2 x 150
XLPE Al
210
200 Circuit A
1 x 95
XLPE Cu
180
1 x 185
XLPE Al
220
1 x 120
XLPE Cu
225
230 Circuit A
1 x 95
XLPE Cu
180
1 x 240
XLPE Al
225
1 x 150
XLPE Cu
230
260 Circuit A
1 x 120
XLPE Cu
185
2 x 150
XLPE Al
265
1 x 240
XLPE Cu
235
285 Circuit A
1 x 150
XLPE Cu
190
2 x 185
XLPE Al
270
2 x 120
XLPE Cu
280
310 Circuit A
1 x 120
XLPE Cu
185
2 x 120
XLPE Al
255
2 x 95
XLPE Cu
270
345 Circuit A
1 x 120
XLPE Cu
185
2 x 150
XLPE Al
265
2 x 95
XLPE Cu
270
375 Circuit A
1 x 150
XLPE Cu
190
2 x 185
XLPE Al
270
2 x 120
XLPE Cu
280
200 Circuit B
1 x 50
XLPE Cu
160
1 x 120
XLPE Al
205
1 x 70
XLPE Cu
205
230 Circuit B
1 x 70
XLPE Cu
170
1 x 150
XLPE Al
210
1 x 95
XLPE Cu
215
260 Circuit B
1 x 95
XLPE Cu
180
1 x 150
XLPE Al
210
1 x 95
XLPE Cu
215
285 Circuit B
1 x 95
XLPE Cu
180
1 x 185
XLPE Al
220
1 x 120
XLPE Cu
225
310 Circuit B
1 x 185
XLPE Cu
190
2 x 185
XLPE Al
270
1 x 240
XLPE Cu
235
345 Circuit B
1 x 185
XLPE Cu
190
2 x 185
XLPE Al
270
2 x 120
XLPE Cu
280
375 Circuit B
1 x 240
XLPE Cu
190
2 x 240
XLPE Al
280
2 x 150
XLPE Cu
290
* Power supply wire section (see diagrams/legend S in chapter ‘Electrical connection’). The disconnect switches are indicated by a 1.
8.4.3 - Selection table of minimum and maximum wire sections 400V-3ph-50Hz + option 150
30HXC
Minimum wire
section (mm2)*
Wire type
L (m)
Maximum wire
section (mm2)*
Wire type
L (m)
080 Opt. 150
1 x 70
XLPE Cu
170
1 x 150
XLPE Al
210
090 Opt. 150
1 x 70
XLPE Cu
170
1 x 185
XLPE Al
220
100 Opt. 150
1 x 95
XLPE Cu
180
1 x 240
XLPE Al
225
110 Opt. 150
1 x 95
XLPE Cu
180
1 x 240
XLPE Al
225
120 Opt. 150
1 x 120
XLPE Cu
185
2 x 95
XLPE Al
195
130 Opt. 150
1 x 120
XLPE Cu
185
2 x 120
XLPE Al
205
140 Opt. 150
1 x 150
XLPE Cu
190
2 x 120
XLPE Al
205
155 Opt. 150
1 x 185
XLPE Cu
190
2 x 150
XLPE Al
210
175 Opt. 150
1 x 185
XLPE Cu
190
2 x 150
XLPE Al
210
190 Opt. 150
2 x 95
XLPE Cu
170
2 x 240
XLPE Al
225
200 Opt. 150 Circuit A
1 x 120
XLPE Cu
185
2 x 150
XLPE Al
265
1 x 185
XLPE Cu
235
230 Opt. 150 Circuit A
1 x 150
XLPE Cu
190
2 x 150
XLPE Al
265
1 x 240
XLPE Cu
235
260 Opt. 150 Circuit A
1 x 185
XLPE Cu
190
2 x 240
XLPE Al
280
2 x 150
XLPE Cu
290
285 Opt. 150 Circuit A
1 x 240
XLPE Cu
190
2 x 240
XLPE Cu
295
310 Opt. 150 Circuit A
1 x 150
XLPE Cu
190
2 x 185
XLPE Al
270
2 x 120
XLPE Cu
280
345 Opt. 150 Circuit A
1 x 185
XLPE Cu
190
2 x 240
XLPE Al
280
2 x 150
XLPE Cu
290
375 Opt. 150 Circuit A
1 x 240
XLPE Cu
190
2 x 240
XLPE Cu
295
200 Opt. 150 Circuit B
1 x 70
XLPE Cu
170
1 x 150
XLPE Al
210
1 x 95
XLPE Cu
215
230 Opt. 150 Circuit B
1 x 70
XLPE Cu
170
1 x 185
XLPE Al
220
1 x 120
XLPE Cu
225
260 Opt. 150 Circuit B
1 x 70
XLPE Cu
170
1 x 185
XLPE Al
220
1 x 120
XLPE Cu
225
285 Opt. 150 Circuit B
1 x 120
XLPE Cu
185
2 x 150
XLPE Al
265
1 x 185
XLPE Cu
235
310 Opt. 150 Circuit B
1 x 185
XLPE Cu
190
2 x 240
XLPE Al
280
2 x 150
XLPE Cu
290
345 Opt. 150 Circuit B
1 x 240
XLPE Cu
190
2 x 240
XLPE Al
280
2 x 150
XLPE Cu
290
375 Opt. 150 Circuit B
2 x 95
XLPE Cu
170
2 x 240
XLPE Cu
295
* Power supply wire section (see diagrams/legend S in chapter ‘Electrical connection’). The disconnect switches are indicated by a 1.