21
5.5 - Electrical data - 30HXC + option 61
30HXC
080 090
100 110 120 130 140 155 175
190
200 230 260
285
310 345 375
Power circuit
Nominal power supply (Un)*
V-ph-Hz 380-3-60
Voltage range
V
342-418
Control circuit supply
The control circuit is supplied via the factory-installed transformer
Nominal operating power input*
kW
56
63
69
78
82
91
103
111
123
129
142
166
189
198
223
249
261
Nominal operating current drawn*
A
114
123 132
146
161
178
198
215
235
257
276
315
352 386
430
469
515
Total harmonic distortion***
%
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Max. operating power input**
kW
87
96
105 118
130
144
159
172
187
212
223
253
281
318
344
374
424
Circuit A**
kW
-
-
-
-
-
-
-
-
-
-
144
159
187
212
172 187
212
Circuit B**
kW
-
-
-
-
-
-
-
-
-
-
79
94
94
106
172
187
212
Max. operating current drawn
(Un - 10%)***
A
162
178
194
218 242
266
294 319
246
392
412
467
519
588
637 692 784
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
266
294
346
392
319
346
392
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
145
173
173
196 319
346
392
Maximum operating current drawn
(Un)***
A
148 162
177
198
220 242
267
290
315
356
374
424
472
534
580 630
712
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
242
267
315
356
290
315 356
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
132
157
157
178
290
315 356
Maximum starting current,
standard unit (Un)
†
A
189 189
203
229
225
279
313
335 360
417
778
908
955
1113 1062 1112
1291
Circuit A***
A
-
-
-
-
-
-
-
-
-
-
646
751
798
935
773 798 935
Circuit B***
A
-
-
-
-
-
-
-
-
-
-
536
641
641
757
773
798 935
Max. starting current/max. current
draw ratio, unit
1,28
1,17
1,15 1,16 1,14 1,15
1,17
1,16 1,15
1,17
2,08 2,14 2,03 2,08 1,84
1,77
1,81
Max. starting current/max. current
draw ratio, circuit A
-
-
-
-
-
-
-
-
-
-
2.67 2.81 2.54 2.63 2.67 2.54 2.63
Max. starting current/max. current
draw ratio, circuit B
-
-
-
-
-
-
-
-
-
4,06 4,08 4,08 4,25
2,67
2,54 2,63
Max. starting current - reduced
current start (Un)
†
A
std
std
std
std
std
std
std
std
std
std
592
667
714
836
821
871
1014
Circuit A
A
-
-
-
-
-
-
-
-
-
-
460
510
557
658
532
557
658
Circuit B
A
-
-
-
-
-
-
-
-
-
-
260
330 330
400
532
557
658
Max. starting current - red. current
start/max. current draw ratio, unit
std
std
std
std
std
std
std
std
std
std
1,58
1,57
1,52
1,57
1,42
1,39
1,42
Circuit A
-
-
-
-
-
-
-
-
-
-
1,90 1,91 1,77
1,85 1,84
1,77
1,85
Circuit B
-
-
-
-
-
-
-
-
-
-
1,97
2,10 2,10 2,25 1,84
1,77
1,85
Three-phase short circuit holding
current
kA
25
25
25
25
25
25
25
25
25
25
N/A N/A N/A N/A N/A N/A N/A
Circuit A
kA
-
-
-
-
-
-
-
-
-
-
25
25
25
25
25
25
25
Circuit B
kA
-
-
-
-
-
-
-
-
-
-
15
15
15
15
25
25
25
Customer standby capacity, unit
or circuit B, for evaporator water
pump connections
‡
kW
8
8
8
11
11
11
15
15
15
15
15
18
18
30
30
30
30
* Based on standardised ARI conditions: Evaporator entering/leaving water temperature 12.2°C and 6.7°C. Condenser entering/leaving water temperature 29.6°C/35°C.
** Power input, compressor, at unit operating limits (evaporator water entering/leaving temperature = 15°C/10°C, condenser entering/leaving water temperature =
45°C/50°C) and a nominal voltage of 460 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
†
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor)
‡
Current and power inputs not included in the values above.
N/A Not applicable