24
Operating range 35% ethylene glycol
Evaporator leaving water temperature, °C
Notes
1. Evaporator ∆T = 4 K max. - condenser ∆T = 5 K
2. Operating range applicable for full and reduced load
3. At full load with a condenser entering water temperature below 20°C, a three-way valve must be used to maintain the correct condensing temperature.
Legend
C Unit operating with a condensing pressure control with an analogue water control valve.
For transient operating modes (start-up and part load), the unit can operate down to a condenser water temperature of 13°C.
D Operation permitted, but performances is not optimized
Condenser entering w
ater temper
atur
e, °C
Condenser entering w
ater temper
atur
e, °C
Evaporator leaving water temperature, °C
50
48
44
20
15
13
D
C
-7
0
4
13 15
Operating range 30% propylene glycol
6.3 - Evaporator water flow (l/s) for 35% ethylene glycol
30HXC
Min.* (closed loop)
Max.**
090
8.0
15.7
110
10.6
21.3
130
12.4
25.1
155
14.5
28.1
175
15.6
33.0
200
20.5
38.0
230
21.0
39.7
260
24.1
48.3
310
29.6
62.0
345
30.2
63.0
* Based on a Reynolds number of 4000
** Based on a water velocity of 3.6 m/s
Evaporator water flow (l/s) for 30% propylene glycol
30HXC
Min.* (closed loop)
Max.**
090
11.1
15.7
110
14.2
21.3
130
16.7
25.1
155
19.1
28.1
175
21.1
33.0
200
25.1
38.0
230
27.4
39.7
260
32.3
48.3
310
40.0
62.0
345
40.6
63.0