5.3 - Electrical data - 30HXC + option 60 with high condensing temperature (options 150/150A)
30HXC
080 090
100 110 120 130 140 155 175
190
200 230 260
285
310 345 375
Power circuit
Nominal power supply (Un)*
V-ph-Hz 460-3-60
Voltage range
V
414-506
Control circuit supply
The control circuit is supplied via the factory-installed transformer
Max. operationg power input*
kW
107 119
131 146
162
180
196
214
231
277
279
312
347
415
429
462 553
Circuit A
kW
-
-
-
-
-
-
-
-
-
-
180
196
231
277
214
231
277
Circuit B
kW
-
-
-
-
-
-
-
-
-
-
99
116
116
138
214
231
277
Max. operating current drawn
(Un - 10%)**
A
167
185
204
227
251
278
303
331
356
427
431
481
534
641
662
712
854
Circuit A
A
-
-
-
-
-
-
-
-
-
-
278
303
356
427
331 356
427
Circuit B
A
-
-
-
-
-
-
-
-
-
-
153
178 178
214
331
356
427
Maximum operating current drawn
(Un)**
A
152
169
185
207
228
253
276
301
324
388
392
438
486
582
602
648
776
Circuit A
A
-
-
-
-
-
-
-
-
-
-
253
276
324
388
301
324 388
Circuit B
A
-
-
-
-
-
-
-
-
-
-
139
162
162
194
301
324 388
Maximum starting current,
standard unit (Un)
†
A
234
264
280 313
302
378
410 436
467
568
1084 1215
1272 1569
1386 1448
1766
Circuit A
†
A
-
-
-
-
-
-
-
-
-
-
939 1039 1096 1372
1065
1096 1372
Circuit B
†
A
-
-
-
-
-
-
-
-
-
-
820
920
920
1175
1065
1096 1372
Max. starting current/max.
current draw ratio, unit
1,44 1,48 1,44 1,45 1,40 1,43
1,39
1,36 1,33 1,44 2,65 2,58 2,41 2,65 2,16 2,06 2,24
Max. starting current/max.
current draw ratio, circuit A
-
-
-
-
-
-
-
-
-
-
3,56 3,52 3,11 3,48 3,32 3,11 3,48
Max. starting current/max.
current draw ratio, circuit B
-
-
-
-
-
-
-
-
-
5,66 5,23 5,23
5,96
3,32 3,11 3,48
Max. starting current - reduced
current start (Un)
†
A
std
std
std
std
std
std
std
std
std
std
744 870
927
1054 1041 1103 1251
Circuit A
A
-
-
-
-
-
-
-
-
-
-
599
694
751
857
720
751 857
Circuit B
A
-
-
-
-
-
-
-
-
-
-
400
435
435
550
720
751 857
Max.starting current - red. current
start/max. current draw ratio, unit
std
std
std
std
std
std
std
std
std
std
1,82 1,85
1,76 1,78
1,62
1,57 1,59
Circuit A
-
-
-
-
-
-
-
-
-
-
2,27
2,35 2,13 2,18 2,24 2,13 2,18
Circuit B
-
-
-
-
-
-
-
-
-
-
2,76 2,47 2,47 2,79
2,24 2,13 2,18
Three-phase short circuit holding
current
kA
25
25
25
25
25
25
25
25
25
25
N/A N/A N/A N/A N/A N/A N/A
Circuit A
kA
-
-
-
-
-
-
-
-
-.
-
25
25
25
25
25
25
25
Circuit B
kA
-
-
-
-
-
-
-
-
-
-
15
15
15
15
25
25
25
Customer standby capacity, unit
or circuit B, for evaporator water
pump connections
‡
kW
8
8
8
11
11
11
15
15
15
15
15
18
18
30
30
30
30
* Power input, compressor, at unit operating limits (evaporator water entering/leaving temperature = 15°C/10°C, condensing temperature = 68°C) and a nominal voltage
of 460 V (data given on the unit name plate).
** Maximum unit operating current at maximum unit power input.
†
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor)
‡
Current and power inputs not included in the values above
N/A Not applicable