CONFIGURATION SCREEN (TYPE 10)
OPTIONS2 (Options Configuration)
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
1
Control Method
0 = Switch
1 = 7 day sched.
2 = Occupancy
3 = CCN
0
CONTROL
2
Loading Sequence Select
1 = Equal loading
2 = Staged loading
1
SEQ
TYPE
3
Lead/Lag Sequence Select
1 = Automatic
2 = Circuit A leads
3 = Circuit B leads
1
LEAD
TYP
4
Cooling Setpoint Select
0 = Single
1 = Dual, remote switch controlled
2 = Dual, clock controlled
3 = 4-20 ma input
0
CLSP
TYP
5
Ramp Load Select
ON/OFF
OFF
RAMP
EBL
6
High LCW Alert Limit
2 to 60
60.0
^F
LCW
LMT
7
Minutes off time
0 to 15
0
min
DELAY
8
Deadband Multiplier
1.0 to 4.0
1.0
Z
GAIN
DISPLAY (STDU SETUP)
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
1
STDU Password
nnnn
1111
PASSWORD
2
Password Enable
enable/disable
enable
PASS
EBL
3
Metric Display
Off/On
Off
DISPUNIT
4
Language
0 = ENGLISH
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES
0
LANGUAGE
CONFIG (TIMED OVERRIDE SETUP)
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
1
Schedule Number
0-99
0
SCHEDNUM
2
Override Time Limit
0-4
0
hours
OTL
3
Timed Override Hours
0-4
0
hours
OTL
EXT
ALARMDEF (Alarm Definition Table)
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
1
Alarm Routing Control
ALRM_CNT
00000000
00000000
2
Equipment Priority
EQP_TYPE
0 to 7
4
3
Comm Failure Retry Time
1 to 240
10
min
RETRY_TM
4
Re-alarm Time
1 to 255
30
min
RE-ALARM
5
Alarm System Name
XXXXXXXX
30_PIC
ALRM_NAM
68
Содержание 30GTN
Страница 6: ...Fig 1 Typical Control Box 080 110 and Associated Modular Units Shown 6 ...
Страница 7: ...Fig 2 24 V Control Schematic Unit Sizes 040 070 7 ...
Страница 8: ...Fig 3 24 V Control Schematic Unit Sizes 080 110 230B 315B 8 ...
Страница 9: ...Fig 4 24 V Control Schematic Unit Sizes 130 210 230A 315A 330A B 420A B 9 ...
Страница 75: ......