Tube Plugging — A leaky tube can be plugged until retub-
ing can be done. The number of tubes plugged determines
how soon cooler must be retubed. Tubes plugged in the fol-
lowing locations will affect the performance of the unit: Any
tube in the area, particularly the tube that thermistor T2 is
adjacent to, will affect unit reliability and performance. Ther-
mistor T2 is used in the freeze protection algorithm for the
controller. If several tubes require plugging, check with your
local Carrier representative to find out how number and lo-
cation can affect unit capacity.
Figure 24 shows an Elliott tube plug and a cross-sectional
view of a plug in place.
Use extreme care when installing plugs to prevent dam-
age to the tube sheet section between the holes.
Retubing (See Table 29) — When retubing is to be done,
obtain service of qualified personnel experienced in boiler
maintenance and repair. Most standard procedures can be fol-
lowed when retubing the 10HB coolers. An 8% crush is rec-
ommended when rolling replacement tubes into the tube
sheet. An 8% crush can be achieved by setting the torque on
the gun at 48 to 50 in.-lb (5.4 to 5.6 N-m).
The following Elliott Co. tube rolling tools are required:
B3400 Expander Assembly
B3401 Cage
B3405 Mandrel
B3408 Rolls
Place one drop of Loctite No. 675 or equivalent on top of
tube prior to rolling. This material is intended to ‘‘wick’’ into
the area of the tube that is not rolled into the tube sheet, and
prevent fluid from accumulating between the tube and the
tube sheet.
Table 29 — Plugs
COMPONENTS FOR
PART NUMBER
PLUGGING
For
Tubes
Brass
Pin
853103-500*
Brass
Ring
853002-570*
For HoleswithoutTubes
Brass
Pin
853103-1*
Brass
Ring
853002-631*
Loctite
No. 675†
Locquic
‘‘N’’†
*Order directly from: Elliott Tube Company,
Dayton, Ohio
†Can be obtained locally.
Tube information follows:
in.
mm
• Tube sheet hole diameter . . . . . . . . . . . . 0.631
16.03
• Tube OD . . . . . . . . . . . . . . . . . . . . . . . . . 0.625
15.87
• Tube ID after rolling . . . . . . . . . . . . . . . 0.581
14.76
(includes expansion due
to
to
to clearance)
0.588
14.94
NOTE: Tubes next to gasket webs must be flush with tube
sheet (both ends).
SIZES 040-050
SIZES 060,070
SIZES 080,090*
SIZES 100,110*
SIZES 130,150*
SIZES 170,190*
SIZE 210*
*And associated modular units (see Table 1).
Fig. 23 — Typical Tube Sheets, Cover Off (Non-Removable Tubes)
Fig. 24 — Eliott Tube Plug
54
Содержание 30GTN
Страница 6: ...Fig 1 Typical Control Box 080 110 and Associated Modular Units Shown 6 ...
Страница 7: ...Fig 2 24 V Control Schematic Unit Sizes 040 070 7 ...
Страница 8: ...Fig 3 24 V Control Schematic Unit Sizes 080 110 230B 315B 8 ...
Страница 9: ...Fig 4 24 V Control Schematic Unit Sizes 130 210 230A 315A 330A B 420A B 9 ...
Страница 75: ......