Table 16 — Example of Temperature Reset (Outdoor Air) Configuration
SUB-MODE
KEYPAD ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
RSET
ENTER
CRST
0
COOLING RESET TYPE
0 = No reset
1 = 4 to 20 mA input
2 = Outdoor Air Temp
3 = Return Fluid
4 = Space Temperature
ENTER
0
Scrolling stops
ENTER
0
Value flashes
2
Select 2
ENTER
2
Change accepted
ESCAPE
CRST
2
Item/Value/Units scrolls again
CRT1
125
Range: 0 to 125 F
ENTER
125
Scrolling stops
ENTER
125
Value flashes
75
Select 75
ENTER
75
Change accepted
ESCAPE
CRT1
75
Item/Value/Units scrolls again
CRT2
0
Range: 0 to 125 F
ENTER
0
Scrolling stops
ENTER
0
Value flashes
50
Select 50
ENTER
50
Change accepted
ESCAPE
CRT2
50
Item/Value/Units scrolls again
DGRC
0
Range: −30 to 30 F
ENTER
0
Scrolling stops
ENTER
0
Value flashes
10
Select 10
ENTER
10
Change accepted
ESCAPE
DGRC
10
Item/Value/Units scrolls again
NOTE: The example below shows how to configure the chiller for temperature reset by an accessory
outdoor-air temperature sensor. The chiller will be configured for a full reset of 10 degrees at 50 F and
no reset at 75 F.
38
Содержание 30GTN
Страница 6: ...Fig 1 Typical Control Box 080 110 and Associated Modular Units Shown 6 ...
Страница 7: ...Fig 2 24 V Control Schematic Unit Sizes 040 070 7 ...
Страница 8: ...Fig 3 24 V Control Schematic Unit Sizes 080 110 230B 315B 8 ...
Страница 9: ...Fig 4 24 V Control Schematic Unit Sizes 130 210 230A 315A 330A B 420A B 9 ...
Страница 75: ......