Table 25 — Configuring Temperature Reset
MODE
GREEN LED)
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
ENTER
DISP
ENTER
TEST
ON/OFF
TEST DISPLAY LEDs
UNIT
ENTER
TYPE
X
UNIT TYPE
OPT1
ENTER
FLUD
X
COOLER FLUID
OPT2
ENTER
CTRL
X
CONTROL METHOD
RSET
ENTER
CRST
X
COOLING RESET TYPE
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM J6-2,5)
2 = Outdoor-Air Temperature
(Connect to TB5-7,8)
3 = Return Fluid (Connect to TB5-5,6)
4 = Space Temperature
CRT1
XXX.X F
NO COOL RESET TEMP
Default: 125 F (51.7 C)
Range: 0 to125 F
Set to 4.0 for CRST= 1
CRT2
XXX.X F FULL COOL RESET TEMP
Default: 0° F (−17.8 C)
Range: 0 to 125 F
Set to 20.0 for CRST=1
DGRC
XX.X °F
DEGREES COOL RESET
Default: 0° F (0° C)
Range: −30 to 30° F (−16.7 to 16.7 C)
The following are examples of outdoor air and space tem-
perature resets:
LEGEND
LWT — Leaving Water (Fluid) Temperature
LEGEND
LWT — Leaving Water (Fluid) Temperature
44