background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 574-086 Rev. A

Printed in U.S.A.

Pg 1 

3-22

Replaces: 574-086

TABLE OF CONTENTS

PAGE

INTRODUCTION   . . . . . . . . . . . . . . . . . . . . . . . . . .   1
R-134a, R-1234ze, or R-513A Applications  . . . . .   1
Scope  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   1
Certifications  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   1
Compressor Offerings  . . . . . . . . . . . . . . . . . . . . .   1
Standard Features   . . . . . . . . . . . . . . . . . . . . . . . .   2
MEDIUM/HIGH TEMPERATURE SYSTEM

DESIGN CONSIDERATIONS   . . . . . . . . . . . . . .   8

Refrigerants and Lubricants   . . . . . . . . . . . . . . . .   8
Environmental Considerations  . . . . . . . . . . . . . .   9
Operating Limits and Controls   . . . . . . . . . . . . . .   9
MEDIUM/HIGH TEMPERATURE SYSTEM OIL 

MANAGEMENT (R-134A, R-1234ZE)  . . . . . . .   11

Oil Pressure Requirements  . . . . . . . . . . . . . . . .   11
Oil Separator Recommendations   . . . . . . . . . . .   11
Oil Heater Recommendations for Air-Cooled

Models  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   11

Oil Level Safety Switch . . . . . . . . . . . . . . . . . . . .   11
Oil Filter  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   11
PCM Controller Operation  . . . . . . . . . . . . . . . . .   12
COMPRESSOR DESIGN PRESSURES   . . . . . . .   15
Compressor Requirements  . . . . . . . . . . . . . . . .   15
Design Pressures  . . . . . . . . . . . . . . . . . . . . . . . .   15
VARIABLE FREQUENCY DRIVE GUIDELINES  .   16
Scope  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   16
Compressor Protection Limits and Guidelines    16
Compressor Input Voltage  . . . . . . . . . . . . . . . . .   16
COMPRESSOR ELECTRICAL DATA  . . . . . . . . .   19
Allowable Voltage Range  . . . . . . . . . . . . . . . . . .   19
ELECTRICAL CONNECTION REQUIREMENTS     19
Power Connections   . . . . . . . . . . . . . . . . . . . . . .   19
Motor Windings Thermistor  . . . . . . . . . . . . . . . .   19
COMPRESSOR ACCESSORIES . . . . . . . . . . . . .   20
Oil Separators  . . . . . . . . . . . . . . . . . . . . . . . . . . .   20
Accessory Kits   . . . . . . . . . . . . . . . . . . . . . . . . . .   20
Economizers  . . . . . . . . . . . . . . . . . . . . . . . . . . . .   20
PCM Controller  . . . . . . . . . . . . . . . . . . . . . . . . . .   20
Compressor Oil  . . . . . . . . . . . . . . . . . . . . . . . . . .   20
VFD Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   20
Motor Cooling Valves & Solenoid Coils  . . . . . .   21
De-Superheating Valves . . . . . . . . . . . . . . . . . . .   21
PACKAGING AND STORAGE REQUIREMENTS   21
Packaging   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   21
Shipping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   21
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   21
Weights and Dimensions  . . . . . . . . . . . . . . . . . .   21

INTRODUCTION

The 06Z screw compressor family is a variable frequency

drive, twin screw, oil injected helical rotor compressor. This

manual is for the Carlyle

® 

variable speed screw compressor

product line, which is comprised of three frame model sizes

06ZC, ZF, and ZJ. Carlyle offers distinct versions of the vari-

able screw compressor for Medium/High Temperature applica-

tions qualified with R-134a, R-1234ze, or R-513A refrigerants.
The following compressor features are offered:

• Variable Vi valve to optimize compressor efficiency.
• Integrated discharge muffler.
• Wide variable speed range to maximize compressor capaci-

ty.

• Standard 2-pole induction motors.

The operational limits, required accessories, and operational

guidelines are contained in this manual must be complied with to

stay within the compressor warranty guidelines.

R-134a,  R-1234ze, or R-513A Applications

The 06Z series compressors are designed for air-cooled R-134a,

R-1234ze, or R-513A applications only.
Each variable screw compressor is designed to be applied with

a dedicated, performance-matched oil separator. This

compressor / oil separator assembly can be applied in a

medium-temperature or high-temperature refrigeration circuit.

Carlyle offers the required oil separators as shown on page 20

of this application guide.

Scope

This application guide is intended to familiarize system design-

ers with the variable screw compressor and to provide technical

information necessary to assure safe and reliable compressor op-

eration.

Certifications

UL and CSA approvals have been obtained for specific  06Z

screw compressor models  applied with R-134a, R-1234ze, or

R-513A.
UL File #: SA4936
CSA File #: SA4936
UL, CSA, and CE approvals have been obtained for all voltage

combinations shown on page 18 of this guide. These compressor

models also comply with the EC Low Voltage and Machinery

Directives.

Compressor Offerings

The three variable speed frame sizes (06ZC, 06ZF, and 06ZJ) are

optimized for application in economized  refrigeration circuits.

Table 1 notes the available variable speed screw compressor

model offering.

06ZC, ZF, ZJ

VARIABLE SPEED TWIN SCREW

COMPRESSOR APPLICATION GUIDE

Содержание 06ZCE1H3AA06013

Страница 1: ...J Carlyle offers distinct versions of the vari able screw compressor for Medium High Temperature applica tions qualified with R 134a R 1234ze or R 513A refrigerants The following compressor features a...

Страница 2: ...capacity may be varied continuously to a lower limit of 22 of the economized compressor s full load capacity for air cooled applications VI CONTROL All 06Z models are supplied with a Vi control valve...

Страница 3: ...3 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1...

Страница 4: ...4 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1 cont...

Страница 5: ...5 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2...

Страница 6: ...6 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2 cont...

Страница 7: ...7 Fig 4 Compressor Physical Data and Connections 06ZJ Frame 3...

Страница 8: ...ISO 220 ASSEMBLY GREASE On occasion it may be necessary to use an assembly grease to re tain an O ring within its groove The following assembly grease is approved for use with the 06Z screwcompressor...

Страница 9: ...Reverse rotation is most likely to occur at initial start up or whenever the wiring to the compressor terminals is disturbed To minimize the possibility for reverse rotation operation Carlyle recommen...

Страница 10: ...Module package P N 6BSB000929 which provides the follow ing safety control functionality Discharge Temperature Monitoring Oil Level Monitoring Oil Flow Rate Supply Monitoring Table 3 Control Points S...

Страница 11: ...he a 500 watt flexible strip heater is recommended The heater should be wired to oper ate when the compressor is OFF This minimizes the migration of refrigerant to the oil stored in the sump Figure 6...

Страница 12: ...ith the following protocol networks BACnet1 Modbus2 N2 Open LonWorks3 requires optional card RS485 Communication Port If applying the Carlyle PCM module the accessories listed in Ta ble 5 are required...

Страница 13: ...13 PCM INPUTS OUTPUTS See Fig 9 for descriptions of the PCM Inputs and Outputs Fig 9 PCM Inputs and Outputs...

Страница 14: ...ssor off Motor Temperature Tm will have the following functions Control a motor cooling valve to provide liquid injection to the motor compartment Turn the compressor off on an overheated motor temper...

Страница 15: ...ON LED INDICATION OUTPUT 4 OUTPUT 5 COMPRESSOR MANUAL RESET REQUIRED HIGH DISCHARGE TEMPERATURE TRIP Solid red Opens De energized OFF Yes HIGH MOTOR TEMPERATURE TRIP Constant blinking Opens De energiz...

Страница 16: ...ERATURE 1 Compressor must be forced to Nominal Voltage as stated in Compressor Input Voltage 2 If operating at max speed reducing speed will allow motor to run on the rated V F curve if motor temperat...

Страница 17: ...17 Fig 13 Compressor Connection Details Fig 14 Sample Compressor Motor Voltage Curves...

Страница 18: ...95 Hz 25 Hz 98 Hz 618 787 865 380V 3 95 Hz 25 Hz 98 Hz 325 414 455 460V 3 95 Hz 25 Hz 98 Hz 269 342 377 06ZJ 325 Hp 380V 3 95 Hz 25 Hz 98 Hz 566 720 792 460V 3 95 Hz 25 Hz 98 Hz 468 596 655 Table 13 A...

Страница 19: ...of the compressor motor The thermistors are an NTC type with a standard resistance of 5000 ohms at 77 F 25 C All 06Z compressor motors are supplied with a spare thermistor to be used if the primary th...

Страница 20: ...GPM 06ZC 30XV50092301 Vertical 3 125 7 06ZF 30XV50122601 Vertical 4 125 7 06ZJ 30XV80004301 Horizontal 4 50 8 Table 19 Accessory Package PART NUMBER COMPRESSOR USAGE 06ZC 06ZF 06ZJ 06ZC660001 X 06ZF66...

Страница 21: ...store the compressors in doors where they are shielded from the weather Outdoor storage is permissible as long as temperatures stay within a temperature range of 40 F to 176 F 40 C to 80 C Weights an...