background image

11

MEDIUM/HIGH TEMPERATURE SYSTEM OIL 

MANAGEMENT (R-134a, R-1234ze)

Oil Pressure Requirements

System pressure is used to generate the oil pressure required to lu-

bricate bearings and provide the oil that acts as a seal between the

screw rotors and the bores. Oil flow and level is monitored con-

tinuously during compressor operation.
The oil pressure must meet the following criteria, based on 

P

DIS-

CHARGE

P

SUCTION

, and 

P

OIL

, as shown in Fig. 7:

1.

P

OIL

 > [0.7 x (

P

DISCHARGE

 – 

P

SUCTION

) + 

P

SUCTION

]

2.

P

OIL

 > [

P

SUCTION

 + 1.0 bar] 75 seconds after start 

The unit control system must monitor the oil pressure differential,

as well as the operating condition, so the compressor can be shut

down if the minimum requirements are not met for any duration

exceeding 15 seconds.
This time delay has two functions: first, to avoid nuisance tripping

during normal and transient operation, and second, to allow the

system sufficient time to develop pressure differential during

start-up.
The compressor must be shut down and prevented from restarting

when the low oil pressure safety is tripped. The safety should be a

manual reset type that locks out compressor operation until the

system is serviced.
Carlyle offers a Compressor Protection Module package to pro-

vide protection against loss of oil flow, oil level, and elevated dis-

charge gas temperature.

Oil Separator Recommendations

The 06Z VFD compressor requires an oil separator. The  com-

bined oil capacity of the oil separator sump, the oil reservoir, and

the oil cooler, should be greater than the values shown in Table 4.

The separator should be selected to provide a maximum oil carry-

over leaving the separator required by that system/application.

Approximate oil flow versus compressor  pressure differential

(Discharge Pressure - Suction Pressure) is shown in Fig. 7. Addi-

tional oil charge may be required for systems that have longer tub-

ing sets.

Fig. 7 — Oil Supply at Compressor

Oil Heater Recommendations for Air-Cooled
Models

For the typical oil separators used with the a 500-watt flexible

strip heater is recommended. The heater should be wired to oper-

ate when the compressor is OFF. This minimizes the migration of

refrigerant to the oil stored in the sump. Figure 6 shows the mini-

mum oil temperatures that must be maintained when the compres-

sor is not operating based on  the outdoor ambient temperature

(OAT). If the application  will allow refrigerant to collect in the

compressor, then a  heater must be installed on the compressor.

Running unit water that is at least 20°F (11°C) below OAT, if pos-

sible,  can be used to prevent refrigerant from collecting in the

compressor. Carlyle recommends that the oil temperature be mon-

itored in warm climate applications and that the oil separator heat-

er be cycled off if oil temperatures reach 190°F (88°C).

Oil Level Safety Switch

An oil level safety switch must be installed in the sump of the oil

separator or the oil reservoir, depending on the  system design.

Carlyle recommends an oil level safety  switch that interrupts

compressor operation if oil levels  are below adequate levels.

Enough oil should remain in the sump when the switch is opened

for the compressor to operate for at least one minute before com-

pletely running out of oil.

Oil Filter

Provisions should be made to isolate the oil filter using  some

combination of shutoff valves and/or check valves, see Fig. 8.

This will allow for the filter element to be replaced without remov-

ing or isolating the charge in the unit.
Because of the long bearing life requirements, filtration for this

compressor is very stringent. The Beta Ratio for  this filter is

greater than or equal to 200 for a five micron particle size evaluat-

ed using ISO 16889 (

(5)



200).

Filter areas must also be sufficient to avoid premature clogging of

the filter during normal operation. An alarm in the controls should

be signaled any time the  pressure drop across the filter (

P

DIS-

CHARGE

 – 

P

OIL

) exceeds 40 psid, indicating the filter needs to be

replaced.

Table 4 — Oil Capacity

COMPRESSOR

MODEL

OIL

SEPARATOR

PART

NUMBER

TYPE

INLET

DIAMETER

(IN.)

OIL

CHARGE

(GPM)

06ZC

30XV50059401

Vertical

3.125

7

06ZF

30XV50122601

Vertical

4.125

7

06ZJ

30XV80004301 Horizontal

4.500

8

 

LEGEND

A/C

— Air-Cooled

Содержание 06ZCE1H3AA06013

Страница 1: ...J Carlyle offers distinct versions of the vari able screw compressor for Medium High Temperature applica tions qualified with R 134a R 1234ze or R 513A refrigerants The following compressor features a...

Страница 2: ...capacity may be varied continuously to a lower limit of 22 of the economized compressor s full load capacity for air cooled applications VI CONTROL All 06Z models are supplied with a Vi control valve...

Страница 3: ...3 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1...

Страница 4: ...4 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1 cont...

Страница 5: ...5 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2...

Страница 6: ...6 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2 cont...

Страница 7: ...7 Fig 4 Compressor Physical Data and Connections 06ZJ Frame 3...

Страница 8: ...ISO 220 ASSEMBLY GREASE On occasion it may be necessary to use an assembly grease to re tain an O ring within its groove The following assembly grease is approved for use with the 06Z screwcompressor...

Страница 9: ...Reverse rotation is most likely to occur at initial start up or whenever the wiring to the compressor terminals is disturbed To minimize the possibility for reverse rotation operation Carlyle recommen...

Страница 10: ...Module package P N 6BSB000929 which provides the follow ing safety control functionality Discharge Temperature Monitoring Oil Level Monitoring Oil Flow Rate Supply Monitoring Table 3 Control Points S...

Страница 11: ...he a 500 watt flexible strip heater is recommended The heater should be wired to oper ate when the compressor is OFF This minimizes the migration of refrigerant to the oil stored in the sump Figure 6...

Страница 12: ...ith the following protocol networks BACnet1 Modbus2 N2 Open LonWorks3 requires optional card RS485 Communication Port If applying the Carlyle PCM module the accessories listed in Ta ble 5 are required...

Страница 13: ...13 PCM INPUTS OUTPUTS See Fig 9 for descriptions of the PCM Inputs and Outputs Fig 9 PCM Inputs and Outputs...

Страница 14: ...ssor off Motor Temperature Tm will have the following functions Control a motor cooling valve to provide liquid injection to the motor compartment Turn the compressor off on an overheated motor temper...

Страница 15: ...ON LED INDICATION OUTPUT 4 OUTPUT 5 COMPRESSOR MANUAL RESET REQUIRED HIGH DISCHARGE TEMPERATURE TRIP Solid red Opens De energized OFF Yes HIGH MOTOR TEMPERATURE TRIP Constant blinking Opens De energiz...

Страница 16: ...ERATURE 1 Compressor must be forced to Nominal Voltage as stated in Compressor Input Voltage 2 If operating at max speed reducing speed will allow motor to run on the rated V F curve if motor temperat...

Страница 17: ...17 Fig 13 Compressor Connection Details Fig 14 Sample Compressor Motor Voltage Curves...

Страница 18: ...95 Hz 25 Hz 98 Hz 618 787 865 380V 3 95 Hz 25 Hz 98 Hz 325 414 455 460V 3 95 Hz 25 Hz 98 Hz 269 342 377 06ZJ 325 Hp 380V 3 95 Hz 25 Hz 98 Hz 566 720 792 460V 3 95 Hz 25 Hz 98 Hz 468 596 655 Table 13 A...

Страница 19: ...of the compressor motor The thermistors are an NTC type with a standard resistance of 5000 ohms at 77 F 25 C All 06Z compressor motors are supplied with a spare thermistor to be used if the primary th...

Страница 20: ...GPM 06ZC 30XV50092301 Vertical 3 125 7 06ZF 30XV50122601 Vertical 4 125 7 06ZJ 30XV80004301 Horizontal 4 50 8 Table 19 Accessory Package PART NUMBER COMPRESSOR USAGE 06ZC 06ZF 06ZJ 06ZC660001 X 06ZF66...

Страница 21: ...store the compressors in doors where they are shielded from the weather Outdoor storage is permissible as long as temperatures stay within a temperature range of 40 F to 176 F 40 C to 80 C Weights an...

Страница 22: ......

Страница 23: ......

Страница 24: ...and without incurring obligations CARLYLE COMPRESSOR DIVISION 2022 Carrier P O Box 4808 Syracuse New York 13221 Phone 1 800 532 5031 Fax 1 315 432 3274 In U S and Puerto Rico 1 800 GO CARLYLE 1 800 46...

Отзывы: