NOTES:

MHA = Max load current at rated voltage

MCC = MHA * 1.1

RLA = MCC / 1.4

Table 11 — VFD Part Number Selection Guide

PART NUMBER

VFD OUTPUT 

VOLTAGE

VFD (kW)

MCC OUTPUT

AT 45C 

(AMPS)

ENCLOSURE 

RATING

WEIGHT (LBS)

DANFOSS 

FUSE PIN

FUSE RATING

HR46ZY014

208/230

160

564

IP54

275

176F3174

800A 700V

HR46ZY030

IP20

HR46ZY006 & 027

380/460

110

212/190

IP54 & IP20

135

176F3171

350A 700V

HR46ZY006 & 028

132

260/240

IP54 & IP20

135

176F3171

350A 700V

HR46ZY008 & 031

160

315/302

IP54 & IP20

135

176F3172

400A 700V

HR46ZY010 & 021

200

395/361

IP54 & IP20

275

176F3173

550A 700V

HR46ZY011 & 022

250

480/443

IP54 & IP20

275

176F8335

630A 700V

HR46ZY019

315

588/535

IP20

275

176F3174

800A 700V

HR46ZY016

400

745/678

IP20

600

176F8592

900A 700V

HR46ZY018

450

800/730

IP20

600

176F8592

900A 700V

Table 12 — Air-Cooled Motor Data R-134a

COMPRESSOR 

BASE MODELS

MOTOR SIZE

MOTOR VOLTAGE 
(VOLTS-PH-FREQ)

FREQ. RANGE

R-134a ELECTRICAL DATA

MIN

MAX

RLA

MHA

MCC

06ZC

130 Hp

200V - 3 - 100 Hz

25 Hz

105 Hz

390

496

546

380V - 3 - 100 Hz

25 Hz

105 Hz

205

261

287

460V - 3 - 100 Hz

25 Hz

105 Hz

169

215

237

06ZF

215 Hp

200V - 3 - 95 Hz

25 Hz

98 Hz

618

787

865

380V - 3 - 95 Hz

25 Hz

98 Hz

325

414

455

460V - 3 - 95 Hz

25 Hz

98 Hz

269

342

377

06ZJ

325 Hp

380V - 3 - 95 Hz

25 Hz

98 Hz

566

720

792

460V - 3 - 95 Hz

25 Hz

98 Hz

468

596

655

Table 13 — Air-Cooled Motor Data R-1234ze

COMPRESSOR 

BASE MODELS

MOTOR SIZE

MOTOR VOLTAGE 
(VOLTS-PH-FREQ)

FREQ. RANGE

R-1234ze ELECTRICAL DATA

MIN

MAX

RLA

MHA

MCC

06ZC

130 Hp

200V - 3 - 100 Hz

25 Hz

105 Hz

312

397

437

380V - 3 - 100 Hz

25 Hz

105 Hz

164

209

230

460V - 3 - 100 Hz

25 Hz

105 Hz

136

173

190

06ZF

215 Hp

200V - 3 - 95 Hz

25 Hz

98 Hz

495

630

693

380V - 3 - 95 Hz

25 Hz

98 Hz

260

331

364

460V - 3 - 95 Hz

25 Hz

98 Hz

216

275

302

06ZJ

325 Hp

380V - 3 - 95 Hz

25 Hz

98 Hz

453

577

634

460V - 3 - 95 Hz

25 Hz

98 Hz

375

477

525

Table 14 — Air-Cooled Motor Data R-513A

COMPRESSOR 

BASE MODELS

MOTOR SIZE

MOTOR VOLTAGE 
(VOLTS-PH-FREQ)

FREQ. RANGE

R-513A ELECTRICAL DATA

MIN

MAX

RLA

MHA

MCC

06ZC

130 Hp

200V - 3 - 100 Hz

25 Hz

105 Hz

398

507

557

380V - 3 - 100 Hz

25 Hz

105 Hz

210

267

294

460V - 3 - 100 Hz

25 Hz

105 Hz

173

220

242

06ZF

215 Hp

200V - 3 - 95 Hz

25 Hz

98 Hz

631

803

883

380V - 3 - 95 Hz

25 Hz

98 Hz

332

423

465

460V - 3 - 95 Hz

25 Hz

98 Hz

275

350

385

06ZJ

325 Hp

380V - 3 - 95 Hz

25 Hz

98 Hz

578

736

809

460V - 3 - 95 Hz

25 Hz

98 Hz

478

608

669

LEGEND

MHA

— Must Hold Amps

MCC

— Maximum Continuous Current

RLA

— Rated Load Amps

Содержание 06ZCE1H3AA06013

Страница 1: ...J Carlyle offers distinct versions of the vari able screw compressor for Medium High Temperature applica tions qualified with R 134a R 1234ze or R 513A refrigerants The following compressor features a...

Страница 2: ...capacity may be varied continuously to a lower limit of 22 of the economized compressor s full load capacity for air cooled applications VI CONTROL All 06Z models are supplied with a Vi control valve...

Страница 3: ...3 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1...

Страница 4: ...4 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1 cont...

Страница 5: ...5 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2...

Страница 6: ...6 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2 cont...

Страница 7: ...7 Fig 4 Compressor Physical Data and Connections 06ZJ Frame 3...

Страница 8: ...ISO 220 ASSEMBLY GREASE On occasion it may be necessary to use an assembly grease to re tain an O ring within its groove The following assembly grease is approved for use with the 06Z screwcompressor...

Страница 9: ...Reverse rotation is most likely to occur at initial start up or whenever the wiring to the compressor terminals is disturbed To minimize the possibility for reverse rotation operation Carlyle recommen...

Страница 10: ...Module package P N 6BSB000929 which provides the follow ing safety control functionality Discharge Temperature Monitoring Oil Level Monitoring Oil Flow Rate Supply Monitoring Table 3 Control Points S...

Страница 11: ...he a 500 watt flexible strip heater is recommended The heater should be wired to oper ate when the compressor is OFF This minimizes the migration of refrigerant to the oil stored in the sump Figure 6...

Страница 12: ...ith the following protocol networks BACnet1 Modbus2 N2 Open LonWorks3 requires optional card RS485 Communication Port If applying the Carlyle PCM module the accessories listed in Ta ble 5 are required...

Страница 13: ...13 PCM INPUTS OUTPUTS See Fig 9 for descriptions of the PCM Inputs and Outputs Fig 9 PCM Inputs and Outputs...

Страница 14: ...ssor off Motor Temperature Tm will have the following functions Control a motor cooling valve to provide liquid injection to the motor compartment Turn the compressor off on an overheated motor temper...

Страница 15: ...ON LED INDICATION OUTPUT 4 OUTPUT 5 COMPRESSOR MANUAL RESET REQUIRED HIGH DISCHARGE TEMPERATURE TRIP Solid red Opens De energized OFF Yes HIGH MOTOR TEMPERATURE TRIP Constant blinking Opens De energiz...

Страница 16: ...ERATURE 1 Compressor must be forced to Nominal Voltage as stated in Compressor Input Voltage 2 If operating at max speed reducing speed will allow motor to run on the rated V F curve if motor temperat...

Страница 17: ...17 Fig 13 Compressor Connection Details Fig 14 Sample Compressor Motor Voltage Curves...

Страница 18: ...95 Hz 25 Hz 98 Hz 618 787 865 380V 3 95 Hz 25 Hz 98 Hz 325 414 455 460V 3 95 Hz 25 Hz 98 Hz 269 342 377 06ZJ 325 Hp 380V 3 95 Hz 25 Hz 98 Hz 566 720 792 460V 3 95 Hz 25 Hz 98 Hz 468 596 655 Table 13 A...

Страница 19: ...of the compressor motor The thermistors are an NTC type with a standard resistance of 5000 ohms at 77 F 25 C All 06Z compressor motors are supplied with a spare thermistor to be used if the primary th...

Страница 20: ...GPM 06ZC 30XV50092301 Vertical 3 125 7 06ZF 30XV50122601 Vertical 4 125 7 06ZJ 30XV80004301 Horizontal 4 50 8 Table 19 Accessory Package PART NUMBER COMPRESSOR USAGE 06ZC 06ZF 06ZJ 06ZC660001 X 06ZF66...

Страница 21: ...store the compressors in doors where they are shielded from the weather Outdoor storage is permissible as long as temperatures stay within a temperature range of 40 F to 176 F 40 C to 80 C Weights an...

Страница 22: ......

Страница 23: ......

Страница 24: ...and without incurring obligations CARLYLE COMPRESSOR DIVISION 2022 Carrier P O Box 4808 Syracuse New York 13221 Phone 1 800 532 5031 Fax 1 315 432 3274 In U S and Puerto Rico 1 800 GO CARLYLE 1 800 46...

Отзывы: