12
PCM Controller Operation
GENERAL DESCRIPTION
The 06Z controller module will function to control compressor’s
Vi control valve and protect the compressor and provide LED
fault status indication for:
• Oil Level Protection
• Oil Flow Protection
• Motor Cooling Protection
• Discharge Temperature Protection
• Transducer Sensor Failure
• Temperature Thermistor Failure
The following controller kit, P/N 6BSB000929, is available
through Carlyle. It is highly recommend the PCM Control-
ler application guide 575-012 be thoroughly reviewed. The
575-012 application guide is located on the Carlyle website
www.carlylecompressor.com.
PCM CONFIGURATION
The PCM can be configured to function in the following modes
of operation:
• Slide Valve Control and Compressor Protection (06T Mod-
els only).
• Vi Piston Control and Compressor Protection (06Z Models
only).
• Compressor protection (both 06Z and 06T models).
Configuring the PCM can be accomplished through:
1. Downloading BACView software to a laptop.
2. Interfacing PCM to a laptop via Carlyle interface cable
P/N: USB-L.
To allow easier transmission of data across a network between the
PCM and the System Controller, the PCM is pre-configured with
the following protocol networks:
• BACnet
1
• Modbus
2
• N2 Open
• LonWorks
3
(requires optional card)
• RS485 Communication Port
If applying the Carlyle PCM module, the accessories listed in Ta-
ble 5 are required.
PCM CONTROLLER DISPLAY FEATURES
To configure and setup the PCM controller, the Virtual BACView
software must be installed on a laptop. Once the software is in-
stalled, the user will use the 12-ft interface cable (Carlyle Part#
USB-L) to communicate between the laptop and the PCM (see
Fig. 8). The Virtual BACView software can be downloaded from
www.carlylecompressor.com under the support software page.
This setup will also be applied to monitor compressor parameters
and field service/troubleshooting work.
Fig. 8 — PCM Local Access Connection
1. BACnet is a registered trademark of ASHRAE (American Society of
Heating, Refrigerating, and Air-Conditioning Engineers).
2. Modbus is a registered trademark of Schneider Electric.
3. LonWorks is a registered trademark of Echelon Corporation.
Table 5 — Required Accessory List
PART NUMBER
DESCRIPTION
APPLICATION
6BSB000929
Medium/High Temperature
Controller Kit
R-134a & R-1234ze
USB-L
PCM Interface Cable
Cable interface
between controller
and laptop
PCM Local Access Connection
Connect the USB-Link to the computer and to the controller’s
Local Access
port.
Connect to
USB port
Connect to
Local Access port
USB Link
7 3/4 in.
12 ft
Содержание 06ZCE1H3AA06013
Страница 3: ...3 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1...
Страница 4: ...4 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1 cont...
Страница 5: ...5 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2...
Страница 6: ...6 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2 cont...
Страница 7: ...7 Fig 4 Compressor Physical Data and Connections 06ZJ Frame 3...
Страница 13: ...13 PCM INPUTS OUTPUTS See Fig 9 for descriptions of the PCM Inputs and Outputs Fig 9 PCM Inputs and Outputs...
Страница 17: ...17 Fig 13 Compressor Connection Details Fig 14 Sample Compressor Motor Voltage Curves...
Страница 22: ......
Страница 23: ......