14

VI PISTON CONTROL
Compressor models 06ZC, 06ZF, 06ZJ are specifically designed

for VFD application ONLY and do not incorporate a slide valve

for capacity control. To optimize compressor efficiency, the com-

pressor is equipped with a Vi piston valve to optimize the com-

pression process, see Fig. 10. The PCM controller will control the

Vi piston automatically based on the compressor’s suction and dis-

charge pressure ratio.

Fig. 10 — Vi Piston Valve Location

PCM CONFIGURATION SETUP
These compressor models will be capacity controlled with an ex-

ternal VFD drive. Therefore the PCM module will be required for

compressor protection and Vi control only. Configuration can be

accessed through the controller setup menu, see Fig. 11
Configure PCM per the following three options (Fig. 12):
1. Vi Piston and Compressor Protection.

2. Vi Piston only.

3. Compressor protection only

Fig. 11 — Controller Setup Menu

Fig. 12 — PCM Configuration Menu

COMPRESSOR PROTECTION
Motor and discharge temperature control for a screw compressor

is critical. Excessive motor and discharge  gas temperatures can

cause premature compressor failure; therefore control of these

temperatures is very  important. The PCM monitors these tem-

peratures through the use of the factory-installed 5K thermistor in

the motor windings and a field-installed 5K thermistor in the com-

pressor discharge temperature thermo-well. When the thermistors

indicate an overheated condition,  the PCM will perform the

following:

• Energize a liquid injection valve, sending cool liquid into

the motor compartment.

• Trip the compressor off.

Motor Temperature (Tm) will have the following functions.

• Control a motor cooling valve to provide liquid injection to

the motor compartment.

• Turn the compressor off on an overheated motor tempera-

ture condition.

• See Table 6: Motor and Discharge Temperature  Control

Points.

Discharge Temperature (Td) will have the following functions.

• Turn the compressor off on a high discharge temperature

condition.

• See Table 6: Motor and Discharge Temperature  Control

Points.

LED FAULT INDICATION
The PCM will provide an LED alarm output signal to the

System Controller when a compressor fault condition arises.

See Table 7.

The Vi piston valve is solenoid controlled
and the following coil voltages can be 
applied...24vac, 120vac, 240vac.

BAC

view

ALARM

C a r l y l e   C o m p r e s s o r   S o f t w a r e   v 2 . 0

C a r l y l e   C o m p r e s s o r   S o f t w a r e   v 2 . 0
C o m p   S t a t u s :   O n       R u n   E n a b l e : O f f

C o m p   S t a t u s :   O n       R u n   E n a b l e : O f f

[   C o n t r o l l e r   S e t u p ]

[   C o n t r o l l e r   S e t u p ]

S u c t i o n   P r e s s u r e :         4 9 . 7 p s i g

S u c t i o n   P r e s s u r e :         4 9 . 7 p s i g

BAC

view

ALARM

- - - - - - - - - - -   C o n t r o l l e r   S e t u p   - - - - - - - - - - -

- - - - - - - - - - -   C o n t r o l l e r   S e t u p   - - - - - - - - - - -

C o n t r o l :       [ V i   P i s t o n   w / C o m p   P r o t e c t ]

C o n t r o l :       [ V i   P i s t o n   w / C o m p   P r o t e c t ]
C o n t r o l   V a r i a b l e :             S u c t i o n   P r e s s

C o n t r o l   V a r i a b l e :             S u c t i o n   P r e s s

[   H o m e ]       [   B A C n e t ]                       [   S t p t s ]

[   H o m e ]       [   B A C n e t ]                       [   S t p t s ]

Table 6 — Motor and Discharge Temperature Control Points

ALC CONTROLLER

INJECTION ON (°F)

INJECTION OFF (°F)

SHUTDOWN 

COMPRESSOR (°F)

MANUALLY RESET 
COMPRESSOR (°F)

TIME DELAY 

REQUIRED BEFORE 

MANUAL RESET 

(seconds)

Discharge 

Temperature (Td)

NA

NA

Td > 225

Td < 175

3

0

Motor Cooling 

Temperature (Tm)

Tm > 240

Tm < 225

Tm > 270

Tm < 225

30

Содержание 06ZCE1H3AA06013

Страница 1: ...J Carlyle offers distinct versions of the vari able screw compressor for Medium High Temperature applica tions qualified with R 134a R 1234ze or R 513A refrigerants The following compressor features a...

Страница 2: ...capacity may be varied continuously to a lower limit of 22 of the economized compressor s full load capacity for air cooled applications VI CONTROL All 06Z models are supplied with a Vi control valve...

Страница 3: ...3 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1...

Страница 4: ...4 Fig 2 Compressor Physical Data and Connections 06ZC Frame 1 cont...

Страница 5: ...5 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2...

Страница 6: ...6 Fig 3 Compressor Physical Data and Connections 06ZF Frame 2 cont...

Страница 7: ...7 Fig 4 Compressor Physical Data and Connections 06ZJ Frame 3...

Страница 8: ...ISO 220 ASSEMBLY GREASE On occasion it may be necessary to use an assembly grease to re tain an O ring within its groove The following assembly grease is approved for use with the 06Z screwcompressor...

Страница 9: ...Reverse rotation is most likely to occur at initial start up or whenever the wiring to the compressor terminals is disturbed To minimize the possibility for reverse rotation operation Carlyle recommen...

Страница 10: ...Module package P N 6BSB000929 which provides the follow ing safety control functionality Discharge Temperature Monitoring Oil Level Monitoring Oil Flow Rate Supply Monitoring Table 3 Control Points S...

Страница 11: ...he a 500 watt flexible strip heater is recommended The heater should be wired to oper ate when the compressor is OFF This minimizes the migration of refrigerant to the oil stored in the sump Figure 6...

Страница 12: ...ith the following protocol networks BACnet1 Modbus2 N2 Open LonWorks3 requires optional card RS485 Communication Port If applying the Carlyle PCM module the accessories listed in Ta ble 5 are required...

Страница 13: ...13 PCM INPUTS OUTPUTS See Fig 9 for descriptions of the PCM Inputs and Outputs Fig 9 PCM Inputs and Outputs...

Страница 14: ...ssor off Motor Temperature Tm will have the following functions Control a motor cooling valve to provide liquid injection to the motor compartment Turn the compressor off on an overheated motor temper...

Страница 15: ...ON LED INDICATION OUTPUT 4 OUTPUT 5 COMPRESSOR MANUAL RESET REQUIRED HIGH DISCHARGE TEMPERATURE TRIP Solid red Opens De energized OFF Yes HIGH MOTOR TEMPERATURE TRIP Constant blinking Opens De energiz...

Страница 16: ...ERATURE 1 Compressor must be forced to Nominal Voltage as stated in Compressor Input Voltage 2 If operating at max speed reducing speed will allow motor to run on the rated V F curve if motor temperat...

Страница 17: ...17 Fig 13 Compressor Connection Details Fig 14 Sample Compressor Motor Voltage Curves...

Страница 18: ...95 Hz 25 Hz 98 Hz 618 787 865 380V 3 95 Hz 25 Hz 98 Hz 325 414 455 460V 3 95 Hz 25 Hz 98 Hz 269 342 377 06ZJ 325 Hp 380V 3 95 Hz 25 Hz 98 Hz 566 720 792 460V 3 95 Hz 25 Hz 98 Hz 468 596 655 Table 13 A...

Страница 19: ...of the compressor motor The thermistors are an NTC type with a standard resistance of 5000 ohms at 77 F 25 C All 06Z compressor motors are supplied with a spare thermistor to be used if the primary th...

Страница 20: ...GPM 06ZC 30XV50092301 Vertical 3 125 7 06ZF 30XV50122601 Vertical 4 125 7 06ZJ 30XV80004301 Horizontal 4 50 8 Table 19 Accessory Package PART NUMBER COMPRESSOR USAGE 06ZC 06ZF 06ZJ 06ZC660001 X 06ZF66...

Страница 21: ...store the compressors in doors where they are shielded from the weather Outdoor storage is permissible as long as temperatures stay within a temperature range of 40 F to 176 F 40 C to 80 C Weights an...

Страница 22: ......

Страница 23: ......

Страница 24: ...and without incurring obligations CARLYLE COMPRESSOR DIVISION 2022 Carrier P O Box 4808 Syracuse New York 13221 Phone 1 800 532 5031 Fax 1 315 432 3274 In U S and Puerto Rico 1 800 GO CARLYLE 1 800 46...

Отзывы: