Parameter
Def.1 Def.2 Def.3 Min Max
UOM SV
type SV
#
Modbus® access
notes
16
Function of probe B2 (see P15)
4
2
2
0
7
---
I
106
234
U
17
Function of probe B3 (see P15)
6
6
6
0
7
---
I
107
235
U
18
Increase cooling/dehumidifi cation set point in sleep
10
10
10
0
255
°C/10 A
18
18
U
19
Decrease heating set point in sleep
10
10
10
0
255
°C/10 A
19
19
U
20
ADC limitation coeffi
cient
6
6
6
0
15
---
I
2
130
U
21
ADC average coeffi
cient
6
6
6
0
15
---
I
3
131
U
22
Select optional compensation probe
0
Compensation disabled
1
Compensation enabled on B1=outside probe
2
Compensation enabled on B3=outside probe
0
0
0
0
2
---
I
4
132
U
23
Set point delta for compensation in cooling
0
Compensation disabled
0
0
0
-99
127
°C/10 A
20
20
U
24
Factor for compensation in cooling
0
Compensation disabled
0
0
0
-20
20
---
A
21
21
U
25
Set point delta for compensation in heating
0
Compensation disabled
0
0
0
-99
127
°C/10 A
22
22
U
26
Factor for compensation in heating
0
Compensation disabled
0
0
0
-20
20
---
A
23
23
U
28
Visibility of output values to supervisor
0
Disabled
1
Enabled
2,3 DO NOT SELECT
0
0
0
0
3
---
I
6
134
U
30
Fan set point (Manual & AUTO)
15
15
15
0
255
°C
A
24
24
U
31
Fan diff erential (Manual & AUTO)
20
20
20
0
255
°C
A
25
25
U
32
Flush off
0
Disabled
>0 Fan off time
2
2
2
0
255
min
I
8
136
U
33
Flush on
0
Disabled
>0 Fan on time
90
90
90
0
255
s
I
9
137
U
34
Flush mode
0
Function disabled
1
Flush function active in cooling, dehumidifi cation &
AUTOMATIC
2
Flush function active in heating & AUTOMATIC OFF
3
Flush function active in heating, cooling,
dehumidifi cation & AUTOMATIC OFF
0
0
0
0
3
---
I
10
138
U
35
Flush time when changing mode
30
30
30
0
255
s
I
11
139
U
36
Select AUTOMATIC with Set point or Comfort
0
Comfort function disabled
(set point can be changed from “acqua” terminal)
1
Enable Comfort
(only ±3 °C change in set point from P01)
0
0
0
0
1
---
I
12
140
U
37
Display (“acqua” terminal)
0
Display set point
1
Display control probe (BT or B1)
2
Display probe B2
3
Display probe B3
4
Display position of modulating valve
5
Display position of modulating damper
0
0
0
0
5
---
I
13
141
U
38
Disable operating mode
1
AUTOMATIC
2
cooling
4
dehumidifi cation
8
ventilation
16
heating
32
autofan
64
sleep
128
ON/OFF timer & display clock
The setting is achieved by adding the values shown
below, each of which corresponds to the disabling of the
corresponding function.
EXAMPLE:
Activation of AUTOMATIC mode only: 2+4+8+16 = 30
0
0
0
0
255
---
I
14
142
U