MasterAria  +030220481 - rel. 1.0 - 12.11.2007

Automatic confi guration of the inputs/outputs and type 
of unit (parameter 91)

To simplify confi guration, one of the three automatic confi gurations can 
be used (columns “Def1, 2, 3” in the table of parameters):

Switch the device off  by pressing the ON/OFF button;

• 

Set parameter 91 according to the values shown in the table below.

• 

Inputs  & 

Outputs

P91=44

AHU 100% 
outside air 

0-10 V valves

P91=45

AHU with 

recirculation

0-10 V valves

P91=46

AHU with 

recirculation

3-point valves

M

ain boar

ID1

ON/OFF

ON/OFF

ON/OFF

ID2

Cooling/Heating

Cooling/Heating

Cooling/Heating

ID3

Serious alarm

Serious alarm

Serious alarm

ID4

Antifreeze alarm

Antifreeze alarm

Antifreeze alarm

ID5

Filter alarm

Filter alarm

Filter alarm

B1

Outlet temperature Outlet temperature Outlet temperature

B2

Heating coil 
temperature

Heating/cooling 
coil temperature

Heating coil 
temperature

B3

Outside 
temperature

Outside 
temperature

Outside 
temperature

NO1

Single-speed outlet 
fan

Single-speed outlet 
fan

Single-speed outlet 
fan

NO2

Disabled

Disabled

Disabled

NO3

Disabled

Disabled

Disabled

Expansion boar

d

NO4

Cool valve

Heating / cooling 
valve

Open heating / 
cooling valve

NO5

Heat valve

Outside air damper

Close heating / 
cooling valve

NO6

Outside damper

Electric heater

Open outside air 
damper

NO7

Disabled

Bypass damper

Close outside air 
damper

Tab. 4.c

Note:

•  The confi gurations corresponding to P91 = 44 and P91 = 45 

require the expansion board with two 0 to 10 Vdc outputs (standard in 
the MasterAria electrical panel), while the confi guration corresponding 
to P91 = 46 requires the expansion board with 4 triacs.
Check that the corresponding inputs and outputs are enabled by 

• 

dipswitch. For example, once having set P91=44, check that dipswitch 
4=ON (see the previous paragraph).
Once parameter 91 has been set, the individual settings for the specifi c 

• 

application can be changed using the parameters corresponding to 
the inputs/outputs (see the following paragraphs).

Identifying/setting the model of unit (parameter 124)

Once automatic confi guration has been completed, make sure that 
MasterAria recognises the type of AHU being managed.

The main setting involves the type of AHU:

100% outside air;

• 

recirculation.

• 

This is set using parameter P124:

P124=0    AHU 100% outside air

Fig. 4.b.a

The AHU with 100% outside air has just one air inlet, that is, from the 
outside, and the air in the environment is no recirculated. In this case, when 

the antifreeze alarm is active the controller stops the fan and switches off  
the optional electric heater.

P124=1  AHU with recirculation

Fig. 4.b.b

In this case, the AHU, as well as taking in air from the outside, recirculated 
the air in the environment. The antifreeze function does not stop the fan 
and, if an electric heater is fi tted, this is not switched off .

Important:

The incorrect confi guration of this parameter may cause damage 

to the AHU!

Confi guration of an AHU with heating/cooling coil only 
(dipswitch 4 = OFF)  
- Confi guration with P91=45

MasterAria does not distinguish between coils for heating or cooling only 
and mixed coils.
The distinction is made by the user, by setting the proportional bands 
accordingly.

Par

Description

Def2

39

Confi guration of output NO4  13 = Valve with 0 to 10 Vdc input for 

cold water (hot/cold water if dip4 = 
OFF) 

40

Confi guration of output NO5 
(see P39)

21 = 0 to 10 Vdc outside damper

41

Confi guration of output NO6 
(see P39)

18 = Output (triac or relay) for man. of 
ON/OFF heaters (with hysteresis) on 
P+I. Set parameters P111, P112. 

42

Confi guration of output NO7 
(see P39)

24 = ON/OFF recovery bypass damper

Tab. 4.d.a

If a modulating valve is used, operation is established by the parameters 
relating to the proportional bands.

In any case, dipswitch 4 must be OFF.

Coil model

Parameters

Heating/Cooling

P115=xx / P116=xx

Heating only

P115=0 / P116=xx

Cooling only

P115=xx / P116=0

Tab. 4.d.b

Par

Description

Def1 Def2 Def3 Min Max

UOM

115

Proportional band for 
cooling valve

40

40

40

0

255

°C /10

116

Proportional band for
heating valve

40

40

40

0

255

°C /10

Содержание MasterAria

Страница 1: ...MasterAria User manual electronic controller...

Страница 2: ......

Страница 3: ...uct should be used or stored in environments that comply with the temperature and humidity limits specified in the manual do not attempt to open the device in any way other than described in the manua...

Страница 4: ......

Страница 5: ...2 Control algorithms 23 4 3 Outlet limits 31 4 3 Notes on settings via serial connection 34 4 4 Alarms 34 4 5 Table of parameters 36 5 SYSTEM DIAGRAMS 42 5 1 System 1 42 5 2 System 2 44 5 3 System 3 4...

Страница 6: ......

Страница 7: ...r the control of single phase and three phase fan motors with the possibility to adjust the maximum cutoff current The product can also be supplied without the electrical panel with the main control b...

Страница 8: ...essing once selects the MasterAria ON time changed using UP DOWN pressing again selects the OFF time and pressing a third time exits the timer programming procedure Increase value UP Decrease value DO...

Страница 9: ...hen runs fan on off cycles at minimum speed to decrease the humidity Fig 2 f Ventilation This operating mode can be disabled by setting parameter 38 8 The mode may be useful for circulating the air in...

Страница 10: ...the corresponding mode 1 AUTOMATIC 2 cooling 4 dehumidification 8 ventilation 16 heating 32 autofan see corresponding paragraph 64 sleep 128 ON OFF timer time display 2 3 Setting the clock and On Off...

Страница 11: ...eep function etc Fitted using the special accessory with a serial port for the network connection of a series of units supervisory system Fig 3 b Expansion board with analogue relay outputs code HYVC0...

Страница 12: ...n In addition it is fitted with an NTC sensor that can be used for room temperature control Fig 3 j 3 2 Installation The electrical panel can be wall mounted or installed in the air handling unit Wall...

Страница 13: ...d to the electrical panel that controls the AHU using 4 plastic spacers manufacturer RICHCO code LCBS 8 01 inserted in the holes on the four corners of the main control board 3 4 MasterAria panel wiri...

Страница 14: ...p Key A1 Main control board A2 Expansion board KR1 KM1 Contactor QS1 Main switch QF1 Circuit breaker V1 Fan FU1 Fuse 3 5 Connection diagrams MasterAria connection diagram L L N DI5 B1 B2 B3 DIP L N re...

Страница 15: ...urchase codes 3 6 Acqua remote terminal Avoid installing the terminal in places where the room temperature measurement may be altered outside walls near doors leading to the outside exposed to the sun...

Страница 16: ...come on in 5 succession if the operation has been completed successfully Other signals indicate problems see the corresponding instruction sheet remove the key and the adapter set the dipswitch to wri...

Страница 17: ...ct the appropriate expansion board if the board supplied is not suitable for the actuators used the board supplied with the MasterAria electrical panel has two 0 to 10 Vdc outputs and two relay output...

Страница 18: ...signal hot water request normally open Contact closed with cold hot water valve or hot water valve only active open with valve deactivated 5 ON OFF hot cold water valve normally open Activated with c...

Страница 19: ...N e DIP4 ON OFF heat cool enable function disabled 2 ON enable digital input 2 for cooling heating changeover for operation of the function see par P56 0 N C Heating N O Cooling 1 N C Cooling N O Heat...

Страница 20: ...eters corresponding to the inputs outputs see the following paragraphs Identifying setting the model of unit parameter 124 Once automatic configuration has been completed make sure that MasterAria rec...

Страница 21: ...on the operating mode heating or cooling Faults with the control probe or the probe on one of the two heat exchangers cause the fan to stop and the valve to close The control probe is selected by dip...

Страница 22: ...see P43 14 14 14 0 14 the economy function corresponds to the sleep function however is activated by digital input Tab 4 f b Important avoid parameter settings that create situations of conflict for...

Страница 23: ...UTOMATIC heating 29 29 29 0 255 C P11 Temperature to enable medium fan speed in heating AUTOMATIC heating 33 33 33 0 255 C P12 Temperature to enable maximum fan speed in heating AUTOMATIC heating 37 3...

Страница 24: ...band P109 around the set point Tab 4 h 3 Extra Flush parameter 35 Note Function active only if the control probe is not probe BT on the acqua terminal This function ensures correct operation when the...

Страница 25: ...n of the set point allowing just a 3 C offset in heating cooling dehumidification and AUTOMATIC mode The set point can be set by serial connection see the corresponding paragraph or on the acqua termi...

Страница 26: ...time 0 the P I algorithm is implemented The following graph shows the case of OPENING when the proportional band for the damper and the hot and cold water valves have the same value with the activati...

Страница 27: ...Min Max UOM 100 Maximum valve stationary time to unlock 0 antistick function disabled 4 4 4 0 255 hrs 101 Forced movement for antistick Considered as a of the maximum travel set 20 20 20 0 100 Tab 4...

Страница 28: ...6 40 40 40 0 255 C 48 Extra flush time with heater 20 20 20 0 255 s Tab 4 h 10 Below is an example of the activation sequence of the MasterAria loads in heating mode the AHU is fitted with a hot cold...

Страница 29: ...meter 118 2 continuous fan operation the fan is started at the same time as the heater and remains on for a time equal to P48 after the heater shuts down As further protection the heater is deactivate...

Страница 30: ...in cooling 0 0 0 0 255 C 10 03 AUTOMATIC mode Set point differential in heating 0 0 0 0 255 C 10 04 AUTOMATIC mode Cooling hysteresis 0 0 0 0 255 C 10 05 AUTOMATIC mode Heating hysteresis 0 0 0 0 255...

Страница 31: ...ed While the outlet limit conditions remain the integral action of the control algorithm is suspended Par Description Def1 Def2 Def3 Min Max UOM 106 Minimum cooling valve heating valve heater outlet t...

Страница 32: ...ater Prog Description Def1 Def2 Def3 Min Max UOM 125 Maximum outlet temperature 127 28 28 28 127 C 126 Outlet limit differential 20 20 20 10 255 C 10 Tab 4 k 127 function disabled Freecooling freeheat...

Страница 33: ...ro parameters P104 and P105 Prog Description Def1 Def2 Def3 Min Max UOM 15 Function of probe B1 6 Outside probe 7 7 7 0 7 16 Funct probe B2 par table 4 2 4 7 17 Funct probe B3 par table 6 6 6 0 7 39 C...

Страница 34: ...l This is especially useful if the MasterAria has the comfort function active e g centralised systems such as hotels offices etc I 83 211 R W Control set point This variable is used to read the value...

Страница 35: ...it may cause irreparable damage to the water coils and the heat recovery unit The antifreeze alarm can be activated by probe P121 P122 activation threshold deactivation threshold or by thermostat Mas...

Страница 36: ...MATIC mode Set point differential in heating 0 0 0 0 255 C 10 A 3 3 U 04 AUTOMATIC mode Cooling hysteresis 0 0 0 0 255 C 10 A 4 4 U 05 AUTOMATIC mode Heating hysteresis 0 0 0 0 255 C 10 A 5 5 U 06 The...

Страница 37: ...134 U 30 Fan set point Manual AUTO 15 15 15 0 255 C A 24 24 U 31 Fan differential Manual AUTO 20 20 20 0 255 C A 25 25 U 32 Flush off 0 Disabled 0 Fan off time 2 2 2 0 255 min I 8 136 U 33 Flush on 0...

Страница 38: ...parameters P111 P117 18 Output triac or relay for man of ON OFF heaters with hysteresis on P I Set parameters P111 P112 19 Open 3 point outside damper 20 Close 3 point outside damper 21 0 to 10 Vdc ou...

Страница 39: ...I 58 186 F 95 SET TO 1 DO NOT MODIFY 1 1 1 0 1 I 61 189 U 97 3 point valve actuator travel time 120 120 120 1 255 s I 63 191 U 99 Minimum P I movement Minimum variation in P I output to move valve for...

Страница 40: ...Enable by probe 2 Enable by digital input 2 2 2 0 2 I 102 230 U 121 Antifreeze activation threshold 2 2 2 28 50 C A 48 48 U 122 Antifreeze deactivation threshold 7 7 7 28 50 C A 49 49 U 123 Antifreez...

Страница 41: ...ED 32 Sleep Eco 4 RESERVED 64 Lock function 8 Remote control 128 RESERVED I 79 207 General flags 2 1 Cooling active 16 RESERVED 2 Heating active 32 RESERVED 4 Comfort active 64 RESERVED 8 Economy 128...

Страница 42: ...T AIR INPUT AIR OUTPUT NO6 NO5 NO1 B1 DI4 BT DI1 DI2 DI5 B3 B2 M NO4 T1 S1 F1 C1 C2 TH1 V1 V2 T2 P1 P2 FAN T3 DI1 DI2 PR T4 M T Fig 5 a Key AI analogue inputs AO analogue outputs F1 filter T1 outside...

Страница 43: ...9 2 P109 2 Fig 5 c Important drawing not to scale for graphics requirements Key P115 proportional band for cooling valve C 10 P116 proportional band for heating valve C 10 P109 dead band C 10 P01 set...

Страница 44: ...AI analogue inputs AO analogue outputs P1 pump conn by installer T1 outside probe V heating cooling coil valve REC heat pump T2 heating cooling coil probe S1 outside damper F1 F2 filter T3 outlet pro...

Страница 45: ...g not to scale for graphics requirements Key P114 proportional band for damper C 10 S outside damper P115 proportional band for cooling valve C 10 TA room temperature control probe P116 proportional b...

Страница 46: ...y AI analogue inputs AO analogue outputs F1 filter T1 outside probe DO digital outputs C heating cooling coil T2 probe heating cooling coil S1_OP open damper P1 pump conn by installer T3 outlet probe...

Страница 47: ...alarm via differential pressure switch connected to digital input DI5 Functional diagrams U S S VF VC P114 30 P116 30 100 P01 TA C P109 2 P114 30 P115 30 P109 2 P119 20 Fig 5 k Important drawing not...

Страница 48: ...ircuits 250 plastic and insulating materials 175 Period of stress across the insulating parts long Category of resistance to fire category D category B UL 94 V0 Class of protection against voltage sur...

Страница 49: ...No2 No3 maximum current VDE0631 6 2 A 250 Vac minimum interval between switching cycles each relay 12 s the manufacturer of the unit that the device is integrated into must guarantee the correct confi...

Страница 50: ...p the power cable relay outputs separate from the cables running to the 0 to 10 Vdc outputs Technical specifications Power supply 230 Vac range 15 to 10 50 60 Hz maximum power input 1 5 VA Screw termn...

Страница 51: ...mper valve 10 KOhm Relay outputs No4 No5 No6 No7 maximum current at 250 Vac EN60730 resistive 2 A inductive 2 A cos j 0 4 60000 cycles type of relay action microswitching 1C For the voltage outputs No...

Страница 52: ...r voltage outputs No4 No5 N06 N07 5m Technical specifications Power supply 230 Vac range 15 to 10 50 60 Hz maximum power input excluding triac loads 1 5 VA Screw termninals max voltage 250 V cable siz...

Страница 53: ...excluding triac loads 1 5 VA Screw termninals max voltage 250 V cable size 14 22 AWG max current see outputs No4 7 Voltage outputs No4 No5 maximum current at 250 Vac for each voltage output 0 3 A typ...

Страница 54: ...er supply and communication signal from main board to RS485 network 7 pin connector reserved for future use Tab 7 p Warnings Use shielded cables for the serial connections 2 wires shield do not use st...

Страница 55: ...cal panel for 4 kW fan motor with adjustable overload protector 0 63 to 1 A CTEDB00005 three phase electrical panel for 4 kW fan motor with adjustable overload protector 1 to 1 6 A CTEDB00006 three ph...

Страница 56: ...Notes...

Страница 57: ...Notes...

Страница 58: ...Notes...

Страница 59: ......

Страница 60: ...ova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency MasterAria 030220481 rel 1 0 12 11 2007 CAREL si riserva la possibilit di apportare modifi che o cam...

Отзывы: