34
ENG
MasterAria +030220481 - rel. 1.0 - 12.11.2007
P127
1
2
3
4
S
t
t
t
AL
ON
OFF
100%
0%
Fig. 4.y.b
Key
4.
T
ROOM
- T
OUTSIDE
1.
cooling
t
time
2.
heating
AL
antifreeze alarm
3.
T
OUTSIDE
- T
ROOM
S
recovery bypass damper
Prog Description
Def1 Def2 Def3 Min
Max
UOM
15
Function of probe B1
6
Outside probe
7
7
7
0
7
---
16
Function of probe B2
(see par. table)
4
2
4
7
---
17
Function of probe B3
(see par. table)
6
6
6
0
7
---
39
Confi g. output NO4
24 ON/OFF recovery
bypass damper
13
13
9
0
24
---
40
Confi guration of output
NO5 (see P39)
14
21
10
0
24
---
41
Confi guration of output
NO6 (see P39)
23
18
19
0
24
---
42
Confi guration of output
NO7 (see P39)
0
24
20
0
24
---
127
Close bypass damper
set point
20
20
20
0
255
°C/10
Tab. 4.n
4.3 Notes on settings via serial connection
All the MasterAria parameters can be viewed and those without write
protection modifi ed via serial connection (PlantVisor and Modbus®).
Below is a short description of the most signifi cant variables (for the
settings, see the summary table of parameters).
Variable
Meaning
Type
SV ind Modbus® ind R/W
Control probe
This variable contains the value of the probe used to control the MasterAria (B1 or BT).
The value considers any off sets, hysteresis, control algorithms etc.
A
74
74
R
Set point setting
This variable is used to read and where necessary overwrite the value of the set point
confi gured on the panel. This is especially useful if the MasterAria has the comfort
function active (e.g. centralised systems such as hotels, offi
ces etc.).
I
83
211
R/W
Control set point
This variable is used to read the value of the control set point used by MasterAria.
The value considers the hysteresis, compensation factors, off sets (e.g.: sleep function),
algorithms etc.
A
76
76
R
Digital inputs & heat/cool
request
Heating/cooling signal: the bits are set when the unit is ON and the set point has not
been reached. Especially useful for energy saving functions.
I 81
209
R
Lock keypad from panel
This variable is used to disable the buttons on the terminal so as to prevent accidental
settings. Useful for centralised systems (hotels, offi
ces etc.).
I
78
206
R/W do not
modify
Tab. 4.o
4.4 Alarms
Below is the table of alarms.
Alarm
Display Eff ect
Notes
Priority
Eeprom fault on power up
A01
Stop fan (with extra fl ush for heater).
Close hot/cold water valves. Switch off heater.
Load defaults or reset from
key
1
Slave offl
ine in CAN network
A02
2
Room probe fault
A03
3
Probe B2 or B3 fault
A04
4
Window alarm A05
A05
5
Circulating pump stopped
A06
6
Local stop
A07
7
Antifreeze alarm
A08
AHU 100% outside air:
AHU with recirculation:
Stop fan (after optional
•
extra fl ush with heater)
Fan operating
•
Close outside damper
•
Activate heating device (heater or
•
valve)
Close outside damper
•
Open cooling valve, with no heating
•
valve or heater
Open heating valve
•
Open cooling valve when
•
no heating valve
Open bypass damper
•
8
Dirty fi lter alarm
A09
Signal only on terminal
9
Tab. 4.p