Carel MasterAria Скачать руководство пользователя страница 26

26

ENG

MasterAria  +030220481 - rel. 1.0 - 12.11.2007

Below is a graph showing an example of confi guration with proportional 
control only (integration time = P108=0) and the trend in the OPENING 
event. 

100%

TA (°C)

P110

P01

P113

P116

P115

P114

P114

P109

P109

U

VC

VF

S

S

Fig. 4.k.a

Key:

P01

set point

U

outputs

P109 dead band

TA

room temperature
(control probe)

P110 heating valve on delta
P113 cooling valve on delta

S

outside damper

P114 damper prop. band

VF

cooling valve

P115 cooling valve prop. band

VC

heating valve

P116 heating valve prop. band

Note that:

the control signal is sent to the actuators outside of the dead band

• 

the valve has a proportional band for heating and another for cooling

• 

the actuators are activated in sequence: fi rst the damper, then the 

• 

valve, which will begin opening outside of the damper proportional 
band, as illustrated in the fi gure. 

In this case, the valve is activated when the damper is completely open, 
with a control signal corresponding to the percentage of opening at that 
point (>0%). As regards CLOSING, fi rst the valve will close completely 
and then the damper will start closing, at a temperature equal to the 
complete closing temperature of the valve plus a ΔT equal to two times 
the dead band:

ΔT = 2*P109

100%

TA (°C)

P110

2xP109

P01

P116

P114

P109

U

VC

S

Fig. 4.k.b

Key:

P01

set point

U

outputs

P109 dead band

TA

room temperature
(control probe)

P110 heating valve on delta
P113 cooling valve on delta

S

outside damper

P114 damper prop. band

VC

heating valve

P116 heating valve prop. band

The behaviour for closing in cooling is similar but opposite.

(*) Note that as there are a maximum of two modulating 0 to 10 Vdc outputs, 
the heater can be controlled with the P+I algorithm only if the damper is on/
off . The activation delta and the proportional band are parameters P111 and 
P117.

Proportional and integral control - PI

If the integration time ≠ 0, the P+I algorithm is implemented. The following 
graph shows the case of OPENING when the proportional band for the 
damper and the hot and cold water valves have the same value, with the 
activation delta set to zero.

OPENING IN HEATING:

the actuators follow a ramp trend, without steps. When the damper 

• 

is completely open, the valve starts opening gradually, as the error 
increases due to the contribution of the integration factor;

CLOSING IN HEATING:

the valve starts closing when the room temperature exceeds point A. 

• 

When the valve is completely closed, the damper starts closing, until 
reaching the minimum position (20%).

BEHAVIOUR IN THE DEAD BAND:

around the set point (±P109) the actuators stop at the position 

• 

calculated when entering the dead band.

100%

TA (°C)

P109

P01

P109

A

P114=P116

P119=20

U

VC

S

Fig. 4.k.c

Key:

P01

set point

U

outputs

P109 dead band

TA

room temperature
(control probe)

P110 heating valve on delta
P113 cooling valve on delta

S

outside damper

P114 damper prop. band

VC

heating valve

P116 heating valve prop. band

The behaviour for opening and closing in cooling is similar but opposite.

Actuator movement control

(parameter 99)

A parameter is available that limits the movements of the valve so as to 
reduce wear and adapt the P+I output to the eff ective resolution for the 
position of the actuator. In fact, a minimum variation in the P+I output can 
be established before the output eff ectively switches (parameter P99).

Reduction in the eff ect of changing modes and/or 
operating parameters (bumpless transfer)

(parameter 107)

The “bumpless transfer” parameter, in response to changes in the P+I 
algorithm control parameters during the normal operation of the unit, 
dampens any swings or over-corrections of the system, especially when 
the algorithm interacts with multiple devices or actuators.

Modulating valve/damper management

(parameters 97,102,103)

For modulating management of the actuators, parameters P15, P16, P17 
must all be set >0.
For correct use of the 3-point actuators, the time taken for complete 
opening or closing must be entered.

Содержание MasterAria

Страница 1: ...MasterAria User manual electronic controller...

Страница 2: ......

Страница 3: ...uct should be used or stored in environments that comply with the temperature and humidity limits specified in the manual do not attempt to open the device in any way other than described in the manua...

Страница 4: ......

Страница 5: ...2 Control algorithms 23 4 3 Outlet limits 31 4 3 Notes on settings via serial connection 34 4 4 Alarms 34 4 5 Table of parameters 36 5 SYSTEM DIAGRAMS 42 5 1 System 1 42 5 2 System 2 44 5 3 System 3 4...

Страница 6: ......

Страница 7: ...r the control of single phase and three phase fan motors with the possibility to adjust the maximum cutoff current The product can also be supplied without the electrical panel with the main control b...

Страница 8: ...essing once selects the MasterAria ON time changed using UP DOWN pressing again selects the OFF time and pressing a third time exits the timer programming procedure Increase value UP Decrease value DO...

Страница 9: ...hen runs fan on off cycles at minimum speed to decrease the humidity Fig 2 f Ventilation This operating mode can be disabled by setting parameter 38 8 The mode may be useful for circulating the air in...

Страница 10: ...the corresponding mode 1 AUTOMATIC 2 cooling 4 dehumidification 8 ventilation 16 heating 32 autofan see corresponding paragraph 64 sleep 128 ON OFF timer time display 2 3 Setting the clock and On Off...

Страница 11: ...eep function etc Fitted using the special accessory with a serial port for the network connection of a series of units supervisory system Fig 3 b Expansion board with analogue relay outputs code HYVC0...

Страница 12: ...n In addition it is fitted with an NTC sensor that can be used for room temperature control Fig 3 j 3 2 Installation The electrical panel can be wall mounted or installed in the air handling unit Wall...

Страница 13: ...d to the electrical panel that controls the AHU using 4 plastic spacers manufacturer RICHCO code LCBS 8 01 inserted in the holes on the four corners of the main control board 3 4 MasterAria panel wiri...

Страница 14: ...p Key A1 Main control board A2 Expansion board KR1 KM1 Contactor QS1 Main switch QF1 Circuit breaker V1 Fan FU1 Fuse 3 5 Connection diagrams MasterAria connection diagram L L N DI5 B1 B2 B3 DIP L N re...

Страница 15: ...urchase codes 3 6 Acqua remote terminal Avoid installing the terminal in places where the room temperature measurement may be altered outside walls near doors leading to the outside exposed to the sun...

Страница 16: ...come on in 5 succession if the operation has been completed successfully Other signals indicate problems see the corresponding instruction sheet remove the key and the adapter set the dipswitch to wri...

Страница 17: ...ct the appropriate expansion board if the board supplied is not suitable for the actuators used the board supplied with the MasterAria electrical panel has two 0 to 10 Vdc outputs and two relay output...

Страница 18: ...signal hot water request normally open Contact closed with cold hot water valve or hot water valve only active open with valve deactivated 5 ON OFF hot cold water valve normally open Activated with c...

Страница 19: ...N e DIP4 ON OFF heat cool enable function disabled 2 ON enable digital input 2 for cooling heating changeover for operation of the function see par P56 0 N C Heating N O Cooling 1 N C Cooling N O Heat...

Страница 20: ...eters corresponding to the inputs outputs see the following paragraphs Identifying setting the model of unit parameter 124 Once automatic configuration has been completed make sure that MasterAria rec...

Страница 21: ...on the operating mode heating or cooling Faults with the control probe or the probe on one of the two heat exchangers cause the fan to stop and the valve to close The control probe is selected by dip...

Страница 22: ...see P43 14 14 14 0 14 the economy function corresponds to the sleep function however is activated by digital input Tab 4 f b Important avoid parameter settings that create situations of conflict for...

Страница 23: ...UTOMATIC heating 29 29 29 0 255 C P11 Temperature to enable medium fan speed in heating AUTOMATIC heating 33 33 33 0 255 C P12 Temperature to enable maximum fan speed in heating AUTOMATIC heating 37 3...

Страница 24: ...band P109 around the set point Tab 4 h 3 Extra Flush parameter 35 Note Function active only if the control probe is not probe BT on the acqua terminal This function ensures correct operation when the...

Страница 25: ...n of the set point allowing just a 3 C offset in heating cooling dehumidification and AUTOMATIC mode The set point can be set by serial connection see the corresponding paragraph or on the acqua termi...

Страница 26: ...time 0 the P I algorithm is implemented The following graph shows the case of OPENING when the proportional band for the damper and the hot and cold water valves have the same value with the activati...

Страница 27: ...Min Max UOM 100 Maximum valve stationary time to unlock 0 antistick function disabled 4 4 4 0 255 hrs 101 Forced movement for antistick Considered as a of the maximum travel set 20 20 20 0 100 Tab 4...

Страница 28: ...6 40 40 40 0 255 C 48 Extra flush time with heater 20 20 20 0 255 s Tab 4 h 10 Below is an example of the activation sequence of the MasterAria loads in heating mode the AHU is fitted with a hot cold...

Страница 29: ...meter 118 2 continuous fan operation the fan is started at the same time as the heater and remains on for a time equal to P48 after the heater shuts down As further protection the heater is deactivate...

Страница 30: ...in cooling 0 0 0 0 255 C 10 03 AUTOMATIC mode Set point differential in heating 0 0 0 0 255 C 10 04 AUTOMATIC mode Cooling hysteresis 0 0 0 0 255 C 10 05 AUTOMATIC mode Heating hysteresis 0 0 0 0 255...

Страница 31: ...ed While the outlet limit conditions remain the integral action of the control algorithm is suspended Par Description Def1 Def2 Def3 Min Max UOM 106 Minimum cooling valve heating valve heater outlet t...

Страница 32: ...ater Prog Description Def1 Def2 Def3 Min Max UOM 125 Maximum outlet temperature 127 28 28 28 127 C 126 Outlet limit differential 20 20 20 10 255 C 10 Tab 4 k 127 function disabled Freecooling freeheat...

Страница 33: ...ro parameters P104 and P105 Prog Description Def1 Def2 Def3 Min Max UOM 15 Function of probe B1 6 Outside probe 7 7 7 0 7 16 Funct probe B2 par table 4 2 4 7 17 Funct probe B3 par table 6 6 6 0 7 39 C...

Страница 34: ...l This is especially useful if the MasterAria has the comfort function active e g centralised systems such as hotels offices etc I 83 211 R W Control set point This variable is used to read the value...

Страница 35: ...it may cause irreparable damage to the water coils and the heat recovery unit The antifreeze alarm can be activated by probe P121 P122 activation threshold deactivation threshold or by thermostat Mas...

Страница 36: ...MATIC mode Set point differential in heating 0 0 0 0 255 C 10 A 3 3 U 04 AUTOMATIC mode Cooling hysteresis 0 0 0 0 255 C 10 A 4 4 U 05 AUTOMATIC mode Heating hysteresis 0 0 0 0 255 C 10 A 5 5 U 06 The...

Страница 37: ...134 U 30 Fan set point Manual AUTO 15 15 15 0 255 C A 24 24 U 31 Fan differential Manual AUTO 20 20 20 0 255 C A 25 25 U 32 Flush off 0 Disabled 0 Fan off time 2 2 2 0 255 min I 8 136 U 33 Flush on 0...

Страница 38: ...parameters P111 P117 18 Output triac or relay for man of ON OFF heaters with hysteresis on P I Set parameters P111 P112 19 Open 3 point outside damper 20 Close 3 point outside damper 21 0 to 10 Vdc ou...

Страница 39: ...I 58 186 F 95 SET TO 1 DO NOT MODIFY 1 1 1 0 1 I 61 189 U 97 3 point valve actuator travel time 120 120 120 1 255 s I 63 191 U 99 Minimum P I movement Minimum variation in P I output to move valve for...

Страница 40: ...Enable by probe 2 Enable by digital input 2 2 2 0 2 I 102 230 U 121 Antifreeze activation threshold 2 2 2 28 50 C A 48 48 U 122 Antifreeze deactivation threshold 7 7 7 28 50 C A 49 49 U 123 Antifreez...

Страница 41: ...ED 32 Sleep Eco 4 RESERVED 64 Lock function 8 Remote control 128 RESERVED I 79 207 General flags 2 1 Cooling active 16 RESERVED 2 Heating active 32 RESERVED 4 Comfort active 64 RESERVED 8 Economy 128...

Страница 42: ...T AIR INPUT AIR OUTPUT NO6 NO5 NO1 B1 DI4 BT DI1 DI2 DI5 B3 B2 M NO4 T1 S1 F1 C1 C2 TH1 V1 V2 T2 P1 P2 FAN T3 DI1 DI2 PR T4 M T Fig 5 a Key AI analogue inputs AO analogue outputs F1 filter T1 outside...

Страница 43: ...9 2 P109 2 Fig 5 c Important drawing not to scale for graphics requirements Key P115 proportional band for cooling valve C 10 P116 proportional band for heating valve C 10 P109 dead band C 10 P01 set...

Страница 44: ...AI analogue inputs AO analogue outputs P1 pump conn by installer T1 outside probe V heating cooling coil valve REC heat pump T2 heating cooling coil probe S1 outside damper F1 F2 filter T3 outlet pro...

Страница 45: ...g not to scale for graphics requirements Key P114 proportional band for damper C 10 S outside damper P115 proportional band for cooling valve C 10 TA room temperature control probe P116 proportional b...

Страница 46: ...y AI analogue inputs AO analogue outputs F1 filter T1 outside probe DO digital outputs C heating cooling coil T2 probe heating cooling coil S1_OP open damper P1 pump conn by installer T3 outlet probe...

Страница 47: ...alarm via differential pressure switch connected to digital input DI5 Functional diagrams U S S VF VC P114 30 P116 30 100 P01 TA C P109 2 P114 30 P115 30 P109 2 P119 20 Fig 5 k Important drawing not...

Страница 48: ...ircuits 250 plastic and insulating materials 175 Period of stress across the insulating parts long Category of resistance to fire category D category B UL 94 V0 Class of protection against voltage sur...

Страница 49: ...No2 No3 maximum current VDE0631 6 2 A 250 Vac minimum interval between switching cycles each relay 12 s the manufacturer of the unit that the device is integrated into must guarantee the correct confi...

Страница 50: ...p the power cable relay outputs separate from the cables running to the 0 to 10 Vdc outputs Technical specifications Power supply 230 Vac range 15 to 10 50 60 Hz maximum power input 1 5 VA Screw termn...

Страница 51: ...mper valve 10 KOhm Relay outputs No4 No5 No6 No7 maximum current at 250 Vac EN60730 resistive 2 A inductive 2 A cos j 0 4 60000 cycles type of relay action microswitching 1C For the voltage outputs No...

Страница 52: ...r voltage outputs No4 No5 N06 N07 5m Technical specifications Power supply 230 Vac range 15 to 10 50 60 Hz maximum power input excluding triac loads 1 5 VA Screw termninals max voltage 250 V cable siz...

Страница 53: ...excluding triac loads 1 5 VA Screw termninals max voltage 250 V cable size 14 22 AWG max current see outputs No4 7 Voltage outputs No4 No5 maximum current at 250 Vac for each voltage output 0 3 A typ...

Страница 54: ...er supply and communication signal from main board to RS485 network 7 pin connector reserved for future use Tab 7 p Warnings Use shielded cables for the serial connections 2 wires shield do not use st...

Страница 55: ...cal panel for 4 kW fan motor with adjustable overload protector 0 63 to 1 A CTEDB00005 three phase electrical panel for 4 kW fan motor with adjustable overload protector 1 to 1 6 A CTEDB00006 three ph...

Страница 56: ...Notes...

Страница 57: ...Notes...

Страница 58: ...Notes...

Страница 59: ......

Страница 60: ...ova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency MasterAria 030220481 rel 1 0 12 11 2007 CAREL si riserva la possibilit di apportare modifi che o cam...

Отзывы: